Batch controller rate/totalizer display – Precision Digital PD6310 User Manual
Page 14

Model PD6210 & PD6310 Batch Controllers
Instruction Manual
14
Batch Controller Rate/Totalizer Display
RATE DISPLAY 
INDICATION 
-99999 to 999999, lead zero blanking. “R” LED illuminates 
while displaying rate. 
BATCH TOTAL & 
GRAND TOTAL 
DISPLAY 
0 to 999,999; automatic lead zero blanking. “T” LED is 
illuminated while displaying batch total. “GT” LEDs are 
illuminated while displaying grand total. Up to 999,999 for 
batch total/preset. Up to 999,999,999 with grand total-
overflow feature. “
oF
” is displayed to the left of grand total
overflow and ▲ LED is illuminated.
BATCH TOTAL 
DECIMAL POINT 
Up to five decimal places or none:
d.ddddd
, d.dddd, d.ddd, d.dd, d.d,
or
dddddd
Total decimal point is independent of rate decimal point.
TOTALIZER
Calculates total based on rate and field programmable 
multiplier to display total in engineering units. Time base 
must be selected according to the time units in which the 
rate is displayed. 
GRAND 
TOTALIZER 
ROLLOVER 
Grand totalizer rolls over when display exceeds 
999,999,999. Relay status reflects display. 
GRAND TOTAL 
ALARMS 
Up to seven, user selectable under setup menu. Any set 
point can be assigned to grand total and may be 
programmed anywhere in the range of the controller for 
grand total alarm indication. Relay 1 should always be 
assigned to batch. 
PROGRAMMABL
E DELAY 
ON RELEASE 
0.1 and 999.9 seconds; applied to the first relay assigned 
to total or grand total. 
If the controller is programmed to reset total to zero 
automatically when the preset is reached, then a delay will 
occur before the total is reset. 
GRAND TOTAL 
RESET 
Via front panel button, external contact closure on digital 
inputs, automatically via user selectable preset value and 
time delay, or through serial communications. 
GRAND TOTAL 
RESET 
PASSWORD 
Grand total passwords may be entered to prevent resetting 
the grand total from the front panel. 
NON-
RESETTABLE 
GRAND TOTAL 
The grand total can be programmed as a non-resettable 
total by entering the password “050873”. 
!
Caution!
Once the Grand Total has been programmed 
as “non-resettable” the feature cannot be 
disabled. 