Safety information – Precision Digital PD6310 User Manual
Page 18

Model PD6210 & PD6310 Batch Controllers
Instruction Manual
18
Modulated
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical Fast
Transients
±2kV AC mains, ±1kV other
Electrostatic
Discharge
±4kV contact, ±8kV air
RFI - Conducted
10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge
±2kV Common, ±1kV Differential
Surge
1KV (CM)
Power-Frequency
Magnetic Field
3 A/m 70%V for 0.5 period
Voltage Dips
40%V for 5 & 50 periods
70%V for 25 periods
Voltage
Interruptions
<5%V for 250 periods
Note:
Testing was conducted on PD6200 and PD6300 series meters
installed through the covers of grounded metal enclosures with
cable shields grounded at the point of entry representing
installations designed to optimize EMC performance. All
hardware is identical to the PD6210 and PD6310 controllers.
Declaration of Conformity available at www.predig.com
SAFETY INFORMATION
!
CAUTION
: Read complete
instructions prior to installation
and operation of the controller.
WARNING
: Risk of electric
shock or personal injury.
Warning!
Hazardous voltages exist within enclosure.
Installation and service should be performed only by
trained service personnel.