beautypg.com

F4 digital input connections, 20 ma output connections, Analog output transmitter power supply – Precision Digital PD6310 User Manual

Page 30: Figure 21: f4 digital input connections

background image

Model PD6210 & PD6310 Batch Controllers

Instruction Manual

30

F4 Digital Input Connections

A digital input, F4, is standard on the meter. This digital input connected
with a normally open closure across F4 and COM, or with an active low
signal applied to F4.

Figure 21: F4 Digital Input Connections

4-20 mA Output Connections

Connections for the 4-20 mA transmitter output are made to the
connector terminals labeled MA OUT. The 4-20 mA output may be
powered internally or from an external power supply.

12-35 VDC

Power

Supply

+

4-20 mA

Input Meter

-

+

R

I-

I+

1

3

2

RELAY1

3

2

1

24 V

-

4-20 mA Input

Remote Display,

Chart Recorder, Etc.

-

+

R

I-

I+

MA OUT

1

3

2

RELAY1

3

2

1

24 V

MA OUT

Figure 22: 4-20 mA Output Connections

Analog Output Transmitter Power Supply

The internal 24 VDC power supply powering the analog output may be
used to power other devices, if the analog output is not used. The I+
terminal is the +24 V and the R terminal is the return.