beautypg.com

Operating area, Connection to the external air intake – MCZ PowerBox COMPACT User Manual

Page 10

background image

Chapter 2

INSTALLATION AND USE MANUAL

page

10

Theoretical notions for installation

Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited

2.3. OPERATING AREA

For proper operation the unit should be placed where air can flow that

is necessary for pellet combustion (this requires about 40 m

3

/h) in

accordance with the standard for installation and current national

standards.
The volume of the room must not be less than 50 m

3.

The air must come in through permanent openings made in walls (in

proximity to the stove) which give onto the outside, with a minimum

cross-section area of 100 cm

2.

These openings must be made in such a way that it is not possible for

them to be obstructed in any way.
Alternatively, the air can be taken from rooms adjacent to the one

which needs ventilating, as long as they are provided with an air intake

from the outside, and are not used as bedrooms or bathrooms, and

provided there is no fire risk such as there is for example in garages,

woodsheds, and storerooms, with particular reference to what is laid

down in current standards.

It is not permissible to install in bedrooms,

bathrooms or showers, or in a room where another

heating appliance is installed (fireplace, stove etc.)

which does not have its own independent air intake.
Locating the stove in a room with an explosive

atmosphere is prohibited.

The floor of the room where the stove is to be

installed must be strong enough to take its weight.

If the walls are not flammable, position the stove with a clearance to

the rear of at least 10 cm.
For flammable walls, keep a minimum distance of 20 cm at the rear, 50

cm on the sides and 150 cm at the front.
If the room contains objects which are believed to be particularly

delicate, such as drapes, sofas and other furniture, their distance from

the stove should be considerably increased.

If the flooring is made of wood, provide a floor

protection surface in compliance with current

national standards.

2.4. CONNECTION TO THE EXTERNAL AIR INTAKE

It is essential that at least as much air must be able to flow into the

room where the stove is installed as is required for proper combustion

in the appliance and for the ventilation of the room. This can be

effected by means of permanent openings in the walls of the room to

be ventilated, which give onto the outside, or by single or collective

ventilation ducts.
For this purpose, on the external wall near the stove, a hole must be

made with a minimum free cross-section of 100 cm². (equivalent to a

round hole of 12 cm diameter or a square hole 10x10 cm), protected by

a grille on the inside and the outside.
The air intake must also:

communicate directly with the room where the stove is installed

Example of realization of air intake

Example of installation of Powerbox

1500 cm

200 cm

200 cm