Appendix a – specifications and optional equipment, A-1 inverter/charger specifications, Appendix a – specifi cations – Magnum Energy MS-G Series User Manual
Page 62: A-1 inverter/charger specifi cations

Page 54
©
2015 Sensata Technologies
Appendix A – Specifi cations
Models
MS2000-G/MS2012-G
MS2812-G
MS4024-G
Inverter Specifi cations
Input battery voltage range
9.0 to 16.9 VDC
18.0 to 33.8 VDC
Absolute maximum DC input
25 VDC
35 VDC
AC output voltage accuracy
120 VAC ±5% (≤ continuous power)
Output frequency and accuracy
60 Hz ± 0.1 Hz
Total Harmonic Distortion (THD)
< 5%
Continuous power output (at 25°C)
2000 VA
2800 VA
4000 VA
Continuous AC output current
16.7 AAC
23 A
33 A
1 msec surge current (amps AC)
50
70
120
100 msec surge current (amps AC)
33
40
82
5 sec surge power (real watts)
3300
3900
5800
30 sec surge power (real watts)
3100
3800
5400
5 min surge power (real watts)
2800
3200
4900
30 min surge power (real watts)
2200
3000
4500
Maximum continuous input current
266 ADC
373 ADC
267 ADC
Inverter effi ciency (peak)
90.6%
90%
93.7%
HBCO/HBCI (High Battery Cut Out/In)
16.9 VDC/16.6 VDC
33.8 VDC/33.2 VDC
LBCO/LBCI (Low Battery Cut Out/In)
9.0 VDC (adj)/12.5 VDC
18.0 VDC (adj)/25.0 VDC
Series Stacking for 120/240 VAC
No
Yes, using two MS4024-G’s
AC Relay Transfer time (minimum)
16 msec
Power Consumption – searching
<8 watts
Power Consumption – inverting (no load)
25 watts
30 watts
25 watts
Output Waveform
Pure Sine Wave
Charger Specifi cations
Continuous charger output at 25°C
100 ADC
125 ADC
105 ADC
Input current for continuous rated output
15 AAC
18 AAC
29 AAC
Charger effi ciency
85%
AC input frequency range
50 to 70 Hz
AC input voltage range
60 to 140 VAC (120 VAC nominal)
Power factor
> 0.95
General Features and Capabilities
Transfer relay capability
30 AAC max each wired input (30AAC total on MS2000-G’s, 50AAC total on other models)
30A max wired output or 20A GFCI output
Five-stage charging capability
Bulk, Absorb, Float, Equalize (requires remote), and Battery Saver™
Battery temperature compensation
Standard with available temp sensor connected (battery temp 0 – 50 °C)
Internal Cooling
0 to 120 cfm variable speed drive using dual 92 mm brushless DC fan
Overcurrent protection
with two overlapping circuits
Over-temperature Protection
on transformer, MOSFETS, and battery
Corrosion protection
PCB’s conformal coated, powder coated chassis/top, and stainless steel fasteners
Safety Listings
ETL listed to UL/cUL 458, UL 1741, CSA C22.2 No. 107.1-01, and meets KKK-A-1822E std**
Warranty
3 years parts and labor (extends to 5 yrs with MMP system)
Environmental Specifi cations
Operating temperature
-20°C to +60°C (-4°F to 140°F)
Non-Operating temperature
-40°C to +70°C (-40°F to 158°F)
Operating humidity
0 to 95% RH non-condensing
Physical Specifi cations
Unit Dimensions (length x width x height)
13.75” x 12.65” x 8.0” (34.9 cm x 32.1 cm x 20.3 cm) [MS2000-G height is 7.0”/17.8 cm]
Shipping Dimensions (l x w x h)
19” x 17” x 13” (48.3 cm x 43.2 cm x 33 cm)
Mounting
Shelf or wall (vents not to face downward unless ME-CB/MPX-CB or MMP is installed)
Unit Weight
42 lb (19.1 kg) /
55 lb (24.9 kg)
55 lb (24.9 kg)
55 lb (24.9 kg)
Shipping Weight
50 lb (22.7 kg) / 63 lb (28.6 kg)
63 lb (28.6 kg)
63 lb (28.6 kg)
Max operating altitude
15,000’ (4570 m)
** MS2000-G models
ETL listed to UL/cUL 458, CSA C22.2 No. 107.1-01, and meet KKK-A-1822E standard.
Specifi cations @ 25°C - Subject to change without notice.
Appendix A – Specifi cations and Optional Equipment
A-1 Inverter/Charger
Specifi cations