Introduction
The left side of MS-G Series inverters are equipped with the following features (refer to Figure 1-3):
13
Exhaust Air Vents – ventilation openings that allow heated air to be removed by the
internal cooling fan.
14
Model/Serial Number Label – includes model/serial number information, date of
manufacture, and inverter and charger specifi cations. See the MS-G Series specifi cations
in Appendix A for more information and a list of available models.
15
AC Access Cover – provides access to the internal AC wiring terminal block (see
Figure 2-10). This terminal block is used to hard wire all inverter AC input and output
wiring connections. Remove the two screws to access the AC wiring terminal block.
Note: The MS2000-G model does not have the AC wiring terminal block.
16
GFCI (Ground Fault Circuit Interrupter) – a 20-amp rated dual outlet that quickly
stops the flow of electricity in the event a ground fault occurs on the device that is plugged
into the inverter.
17
HOT 1 Input – this 30-amp circuit breaker protects the unit’s internal charger wiring
and pass-thru relay while in Standby mode. The circuit breaker pops out when it opens—
press in to reset. The input circuit breaker is not branch-rated, therefore branch-rated
circuit breakers must be installed in the inverter’s input wiring.
18
GFCI Output – this 20-amp circuit breaker is branch-rated and protects the wiring to the
GFCI outlet. This circuit breaker pops out when it opens—press in to reset. It can also be
manually pulled to disconnect the inverter’s loads.
CAUTION: The inverter’s internal AC transfer relay is rated for 30 amps per wired input
(not the GFCI circuit). The pass-thru current must be no greater than 30 amps per leg
or damage to the relays may occur.
14
15
13
18
17
AC Access Cover
Model/Serial
Number Label
HOT 1 Input
Circuit Breaker
GFCI Output
Circuit Breaker
Exhaust
Air Vents
(back and
right side)
GFCI
16
Figure 1-3, Left Side Features