beautypg.com

Magnum Energy MS-G Series User Manual

Page 31

background image

©

2015 Sensata Technologies

Page 23

Installation

2.5.6

AC Wiring Confi gurations (MS2012-G, MS2812-G, MS4024-G)

The following table provides the different wiring confi gurations for installing and connecting the AC

conductors to and from the inverter (refer to Figures 2-11 to 2-14 for installation drawings showing

these confi gurations). Refer to Table 2-4 (and Figures 2-15 & 2-16) for the MS2000-G model.

Table 2-3, AC Input/Output Wiring Confi gurations

SI

Single In

SI/SO

Single In/

Single Out

(≤ 30A output)

SI/SO

Single In/

Single Out

(≤ 50A output)

DI/SO

Dual In/

Single Out

AC Input

Source

1

120 VAC @ ≤30

amps

120 VAC @ ≤30

amps

120 VAC @ >30

amps

(60 amps max.)

120/240 VAC

(or 2 separate

legs of 120 VAC)

2

@ ≤30 amps/leg

Reason to Use

Have an 120

VAC source that

is ≤30 amps,

and using the

GFCI outlet to

connect loads.

Have an 120 VAC

source that is ≤30

amps.

Requires a

separate inverter

sub-panel.

Have an 120 VAC

source that is

>30 amps.

Requires a

separate inverter

sub-panel.

Want dedicated

pass-thru while

AC source is on.

Requires a

separate inverter

sub-panel.

Appropriate

Models

MS2012-G

MS2812-G

MS4024-G

MS2012-G

MS2812-G

MS4024-G

MS2012-G

MS2812-G

MS4024-G

MS2012-G

MS2812-G

MS4024-G

Maximum

Input Breaker

Required

-

Minimum

Wire Size

(AWG)

30A

(single pole)

-

#10 AWG

(In)

30A

(single pole)

-

#10 AWG In

(split into two #10

AWG for HOT 1 &

HOT 2 IN)

#10 AWG Out

(HOT 2 OUT)

60A

(single pole)

-

#6 AWG In

(split into two

#10 AWG for

HOT 1 & HOT 2

IN)

#10 AWG Out

(HOT 2 OUT)

30A

(dual pole)

-

#10 AWG

(In & Out)

Maximum

Inverter Pass-

thru Capacity

-

Output

Confi gurations

2400W

-

20A @ 120 VAC

3600W

-

30A @ 120 VAC =

3600W

(HOT 2 OUT)

or

20A @ 120 VAC =

2400W

(GFCI outlet)

6000W

-

30A @ 120 VAC

(HOT 2 OUT)

and

20A @ 120 VAC

(GFCI outlet)

6000W

-

30A @ 120 VAC

(HOT 2 OUT)

and

20A @ 120 VAC

(GFCI outlet)

Wiring

Diagram

Figure 2-11

Figure 2-12

Figure 2-13

Figure 2-14

Note

1

– AC Source is from either the utility/grid power (i.e., shorepower) or an AC generator.

Note

2

– If two legs of 30A @ 120 VAC are used, they must be from the same source (i.e., have a common

neutral). For example, 2 legs from a 3-phase source can be used.