beautypg.com

6 grounding inverters, Installation 2.6 grounding inverters – Magnum Energy MS-G Series User Manual

Page 40

background image

Page 32

©

2015 Sensata Technologies

Installation

2.6 Grounding

Inverters

The inverter/charger should always be connected to a permanent, grounded wiring system.

An inverter system that is properly grounded will limit the risk of electrical shock, reduce radio

frequency noise from the inverter, and minimize excessive surge voltages induced by lightning. This

is done by ensuring there is a well-defi ned, very low-resistance path from the electrical system to

the grounding system. This low-resistance path helps stabilize the electrical system voltage with

respect to ground and carries fault currents directly to ground if the electrical system malfunctions.
To understand how the conductors in the electrical circuit will be connected to the system ground,

the following terms should be understood:
• Grounded

Conductor

(GC): The wire/cable in the electrical system that normally carries

current (usually AC neutral and/or the DC negative), and is intentionally connected or “bonded”

to the ground system. This wire, or the ends of this wire, should be colored white or gray.

• Equipment Grounding Conductor (EGC): A wire/cable that does not normally carry current

and is used to connect the exposed metal parts of equipment—that might be accidentally

energized—to the grounding electrode system or to the grounded conductor. This wire, or the

ends of this wire, should be green or green with a yellow stripe; this wire can be bare copper.

• Grounding Electrode Conductor (GEC): The wire/cable that does not normally carry

current and connects the grounded conductor and/or the equipment grounding conductor to

the grounding electrode at the service equipment.

• Grounding

Electrode

(GE): A ground rod or conducting element that establishes an electrical

connection to the earth.

• System bonding jumper (SBJ): The connection between the grounded circuit conductor in

the electrical system and the equipment grounding conductor at a separately derived system.

The MS-G Series inverter/charger uses both AC and DC power; however, the AC electrical system

is isolated from the DC electrical system by an internal transformer. Although this inverter/charger

has two electrical systems, each electrical system must be properly grounded and connected to

a common “earth” reference. Refer to Figure 2-17.
For proper grounding, each electrical system must connect all exposed metal parts of equipment

(via equipment grounding conductors – EGC) and one of the current-carrying conductors (grounded

conductor – GC) together at a common point (ground busbar – GBB), usually by a system bonding

jumper (SBJ) in an electrical service disconnect panel. The common point of each electrical system

is then connected (via grounding electrode conductor – GEC) to the common ground reference,

such as a ground rod (grounding electrode – GE). This connection to earth should only be made

at one point in each electrical system; otherwise, parallel paths will exist for the currents to fl ow.

These parallel current paths would represent a safety hazard and are not allowed in installations

wired per the NEC/CEC.

Figure 2-17, Grounding System for MS-G Series

AC

DC Service

Panel

AC Service

Panel

DC Electrical System

AC Electrical System

Neutral

Positive

Negative

DC

Grounding

System

Negative

SBJ

GC

GE

GEC-AC

EGC

AC Ground

DC Ground

SBJ

EGC

GC

Neutral

Hot

GEC-DC

GE

GE

GBB

GBB

Grounding Electrode

(AC and DC sides shared)

Grounding Electrode

(DC side dedicated)

Grounding Electrode

(AC side dedicated)

or

or

MS Series Inverter/Charger