Maintenance/Troubleshooting
Operating Instructions Powador 12.0 TL3-20.0 TL3
Page 49
Status
Display
Explanation
Action
FS 17
Shutting down
Powador-protect
The activated grid and system
protection has been tripped.
"
Wait for reactivation.
"
Notify your
authorised
electrician if the fault
occurs several times.
E
FS 18
Resid. current
shutdown
Residual current was detected. The
feed-in was interrupted.
"
Notify your
authorised
electrician.
E
FS 19
Generator
insulation fault
There is an insulation fault on the PV
generator. The feed-in was interrupted.
"
Notify your
authorised
electrician if the fault
occurs several times.
E
FS 30
Voltage trans. fault
The current and voltage measurements
in the inverter are not within acceptable
range.
-
-
FS 32
Self test error
The internal grid separation relay test
has failed.
"
Notify your
authorised
electrician if the fault
occurs several times.
E
FS 33
DC feed-in error
The DC feed-in has exceeded the
permitted value. This DC feed-in can
be caused by grid conditions and may
not necessarily indicate a fault.
"
Notify your
authorised
electrician if the
fault occurs multiple
times.
E
FS 34
Internal
communication
error
A communication error has occurred
in the internal data transmission.
"
Notify your
authorised
electrician.
E
"
Check the data cable.
FS 35
Protection
shutdown SW
Protective shutdown of the software
(AC overvoltage, AC overcurrent,
DC link overvoltage, DC overvoltage,
DC overtemperature).
Not a fault Grid-related
shutdown, the grid connects
again automatically.
FS 36
Protection
shutdown HW
Protective shutdown of the hardware
(AC overvoltage, AC overcurrent,
DC link overvoltage).
Not a fault Grid-related
shutdown, the grid connects
again automatically.
FS 38
Generator
overvoltage error
The voltage of the DC generator
is too high. The PV generator is
configured incorrectly.
"
Notify your
authorised
electrician.
E
FS
41
42
Line failure:
Under voltage L1,
Over voltage L1,
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
"
Notify your
authorised
electrician.
E
43
44
Under voltage L2,
Over voltage L2,
45
46
Under voltage L3,
Over voltage L3,
FS 47
Grid failure: phase-
to-phase volt.
The measured line-to-line voltage is
outside of the tolerance limits.
Table 3:
Operating status and fault messages on the display