Installing the inverter
Page 22
Operating Instructions Powador 12.0 TL3-20.0 TL3
Authorised electrician
7.2.2.5 Unconnected inputs
NOTE
If one of the MPP trackers (A or B) is not used, then it must be short-circuited, otherwise faults can
occur in the self-test of the unit and the feed-in operation is not guaranteed. The short-circuiting of
an MPP tracker does not result in the device being damaged.
The recommended standard connection or the parallel input connection should always be used as
a matter of course before an MPP tracker is short-circuited and therefore remains unused.
Electrical data for unused MPP trackers
Connecting the DC inputs
Number of modules per string: n
1
=n
2
=n
m
P
max
Per string < 0.5 * max. recommended PV generator power P
max
on the
MPP tracker used < max. power per tracker
I
max
< max. rated current (DC)
1
A
B
2
3
4
U
MPP
...
n
1
n
2
n
m
=
=
Figure 11: Parallel input with Y-adapter, short-circuits the unused MPP Tracker B