4 starting up the inverter, Starting up the inverter, 1 switching on the inverter – KACO Powador 10.0 - 20.0 TL3 User Manual
Page 28

EN
EN
Installing the inverter
Page 28
Operating Instructions Powador 12.0 TL3-20.0 TL3
Authorised electrician
7.4
Starting up the inverter
DANGER
Lethal voltages are still present in the terminals and cables of the inverter even after
the inverter has been switched off and disconnected.
Severe injuries or death may occur if the cables and terminals in the inverter are touched.
Only appropriately qualified and authorised electricians may start up the inverter.
FR
Attachment of safety label in accordance with UTE C 15-712-1
The code of practice UTE C 15-712-1 requires that, upon
connection to the French low-voltage distribution network,
a safety sticker showing a warning to isolate both power
sources when working on the device must be attached to
each inverter.
"
Attach the provided safety sticker visibly to the outside of
the inverter housing.
ATTENTION
Présence de deux
sources de tension
- Réseau de distribution
-Panneaux photovoltaïques
Isoler les deux sources
avant toute intervention
7.4.1 Switching on the inverter
↻ The inverter has been mounted and electrically installed.
↻ The PV generator supplies a voltage above the configured start voltage.
1. Connect the grid voltage using the external circuit breakers.
2. Connect the PV generator using the DC isolator switch (0
→ 1).
»
The inverter begins to operate.
»
During the initial start-up: Follow the instructions of the New Connection Wizard.