Configuration and operation – KACO Powador 10.0 - 20.0 TL3 User Manual
Page 39

EN
Configuration and Operation
Operating Instructions Powador 12.0 TL3-20.0 TL3
Page 39
Country-
spec. Setting
Menu
level
Display/settings
Action in this menu/meaning
0
1
2
3
1
Powador-protect
Configures the support for grid shutdown by a Powador
protect connected to the digital input of the inverter.
↻ For Auto/On: A Powador protect is operating in
the photovoltaic system and is connected to the
inverter at the digital input/output.
"
Auto: The inverter automatically detects a Powador-
protect integrated into the photovoltaic system.
"
On: The digital signal of the Powador protect must
be present to the digital input of the inverter for the
inverter to start with feed-in.
"
Off: The inverter does not check whether a Powador-
protect is integrated into the photovoltaic system.
0
1
2
3
1
Iso.resistor
"
Set threshold value (in 1 kOhm steps) at which the
insulation monitor reports a fault.
DE-MSp, FR,
AT, PL, RU,
ES, TH, ZA
0
1
2
3
1
Activate FRT
The inverter supports dynamic grid stabilisation
(Fault Ride-Through) in accordance with the BDEW
Medium Voltage Directive.
"
Specify constant k.
"
Specify the dead band.
"
Activate or deactivate FRT.
DE, BE, FR,
GB, IL, IT, AT,
PL, RU, ES,
KR, TH, ZA
0
1
2
3
1
Reactive power
"
Open the menu: Press the right arrow button or
the OK button.
"
Activating idle power process: select process and
press OK. The active process is highlighted.
0
1
2
3
2
cos-phi
specification
"
Configure power factor.
"
If a power factor not equal to 1 is selected: Select the
type of phase shift (under-excited/over-excited).
DE-MSp, FR,
GB, IL, IT, AT,
PL, RU, ES,
KR, TH
0
1
2
3
2
Q const.
"
Set the idle power Q (in %) to a fixed value.
"
Select the type of phase shift (under-excited/
over-excited).
DE, BE, GB, IT,
AT, ES, KR, UD
0
1
2
3
2
cos-phi(P/Pn)
"
Open the menu: Press the right arrow button or
the OK button.
GB, IT, AT, ES,
KR
0
1
2
3
3
Lock-in voltage
"
Power range set as % of rated voltage, where the
network support process is active.
0
1
2
3
3
Lock-out
voltage
DE, BE, FR,
GB, IL, IT, AT,
PL, RU, ES,
KR, TH, UD
0
1
2
3
3
Number of
nodes
This option defines how many support points can be
defined in the subsequent menu. The maximum number
of configurable support points depends on the selected
grid type.
"
Specify the number of support points for the idle
power characteristic curve.
0
1
2
3
3
1., 2. ...Support
point
"
Specify the power factor for the 1st, 2nd (etc.)
support point
"
If a power factor not equal to 0 is selected: Select the
type of phase shift (under-excited/over-excited).