7 installing the inverter, 1 opening the connection area, Installing the inverter – KACO Powador 10.0 - 20.0 TL3 User Manual
Page 15: Opening the connection area, 7installing the inverter

EN
Installing the inverter
Operating Instructions Powador 12.0 TL3-20.0 TL3
Page 15
Key
1
Fixings for mounting
4
Detachment protector
2
Mounting plate
5
Suspension brackets (back of housing)
3
Screws for mounting
A
•
Horizontal distance between the two inverters /
inverter and the wall
•
Distance in front
25 cm
B
Distance between the inverter and the ceiling / floor
50 cm
C
vertical distance between the two inverters
70 cm
Mounting the inverter
1. Mark the positions of the drill holes using the cut-outs in the mounting plate.
NOTE: The minimum clearances between two inverters, or the inverter and the ceiling/floor have already been
taken into account in the diagram.
2. Fix mounting plate to the wall with the supplied mounting fixtures.
Make sure that the mounting plate is oriented correctly.
3. Hang the inverter on the mounting plate using the suspension brackets on the back of the housing.
4. Fix the inverter with the enclosed screws to the detachment protector at the connection area.
»
The mounting of the inverter is complete. Continue with the installation.
7
Installing the inverter
DANGER
Lethal voltages are still present in the terminals and cables of the inverter even after the
inverter has been switched off and disconnected.
Severe injuries or death may occur if the cables and terminals in the inverter are touched.
Only appropriately qualified and authorised electricians may open and install the inverter.
The inverter must be mounted in a fixed position before being connected electrically.
›
Observe all safety regulations and current technical connection specifications of the responsible
power supply company.
›
Disconnect the AC and DC sides.
›
Secure both sides against being inadvertently switched back on.
›
Ensure that the AC and DC sides are completely isolated and voltage free.
›
Connect the inverter only after the aforementioned steps have been taken.
7.1
Opening the connection area
Opening the connection area
↻ You have mounted the inverter on the wall.
1. Unscrew the four Torx screws on the front side of the connection cover (blue).
2. Pull down the connection cover.
»
Make the electrical connection.