4 technical data, 1 electrical data, Technical data – KACO Powador 10.0 - 20.0 TL3 User Manual
Page 10: Electrical data, 4technical data

EN
EN
Technical Data
Page 10
Operating Instructions Powador 12.0 TL3-20.0 TL3
4
Technical Data
4.1
Electrical data
Input levels
12.0 TL3
14.0 TL3
18.0 TL3
20.0 TL3
DC MPP range from [V] to [V]*
350 ... 800
350 ... 800
420 ... 800
460 ... 800
Operating range from [V] to [V]
200 ... 800
Starting voltage [V]*
250
Open circuit voltage [V]
1,000 (start up to 1,000)
Rated current max. [A]
2 x 18.6
Max. power per tracker [W]
10200
12800
12800
12800
Number of strings
2 x 2
Number of MPP controls
2
Polarity safeguard
Short-circuit diode
DC overvoltage safety class
III
DC overvoltage category
II
*At DC voltages below the MPP range the maximum rated current reduces the maximum input power.
**For PV generators with MPP voltages below the MPP range of the inverter: set the start voltage in the menu.
Output levels
12.0 TL3
14.0 TL3
18.0 TL3
20.0 TL3
Rated power [VA]
10000
12500
15000
17000
Grid voltage [V]
400/230 (3/N/PE)
Rated current [A]
3 x 14.5
3 x 18.1
3 x 21.8
3 x 24.6
Rated frequency [Hz]
50 / 60
cos phi
0.80 inductive to 0.80 capacitive
Number of feed-in phases
3
Distortion factor [%]
5.5
AC overvoltage safety class
III
AC overvoltage category
III
General electrical data
12.0 TL3
14.0 TL3
18.0 TL3
20.0 TL3
Max. efficiency [%]
98.0
98.0
98.0
97.9
European efficiency [%]
97.5
97.6
97.7
97.6
Make current [A] and ON duration [ms]
4.52 / 4.4
Internal consumption: night [W]
1.5
Feed-in starts at [W]
20
Circuit design
Transformerless
Grid monitoring
Country-specific