Configuration and Operation
Page 34
Operating Instructions Powador 12.0 TL3-20.0 TL3
Country-
spec. Setting
Menu
level
Display/settings
Action in this menu/meaning
0
1
2
3
2
Day display
Displays the recorded operating data graphically.
1. Select the measured value to be displayed.
Supported measured values:
•
Grid power P(grid)
•
DC power per string P(PV) 1-2
•
DC voltage per string U(PV) 1-2
•
Unit temperature
2. Select a day.
3. Press the OK button.
»
The display shows the selected data.
"
Press any button to return to the previous menu.
0
1
2
3
2
Month display
Displays the recorded operating data graphically.
1. Select a month.
2. Press the OK button.
»
The display shows the selected data.
"
Press any button to return to the previous menu.
0
1
2
3
2
Year display
Displays the recorded operating data graphically.
1. Select a year.
2. Press the OK button.
»
The display shows the selected data.
"
Press any button to return to the previous menu.
0
1
2
3
2
CSV log data
"
Open the menu: Press the right arrow button or
the OK button.
0
1
2
3
3
Decimal separator
"
Select decimal sign for export of saved operating
data.
0
1
2
3
3
Save to USB
In this menu, you can export the saved operating data
to a connected USB storage device.
↻ You have connected a USB storage device to the
inverter.
1. Select the data to be exported (year, month or day).
2. Press the OK button.
»
The inverter writes the data to a connected USB
storage device.
0
1
2
3
0
“Settings” menu
"
Open the menu: Press the right arrow button or
the OK button.
0
1
2
3
1
Language
"
Select the desired language for the user interface.
0
1
2
3
1
Def. total yield
You can set the total yield to any value, for example,
when you have received a replacement unit and want to
continue the recording from the present value.
"
Select the “Save” button and confirm with the OK
button.
0
1
2
3
1
Interface
"
If the inverter is a terminal unit: Activate termination
(“Bus termination” menu option)
"
Assign a unique RS485 bus address to the inverter
(“RS485 address” menu option). The address must
not be the same as that of any other inverter or
a proLOG unit.