KACO Powador 10.0 - 20.0 TL3 User Manual
Page 37

EN
Configuration and Operation
Operating Instructions Powador 12.0 TL3-20.0 TL3
Page 37
Country-
spec. Setting
Menu
level
Display/settings
Action in this menu/meaning
0
1
2
3
0
“Parameters” menu
"
Press the right arrow button or the OK button.
NOTE: The inverter does not display the “Parameters”
menu in the standard configuration. To display the
Parameters menu:
1. Open the menu.
2. Simultaneously hold down the up and down
buttons for several seconds.
0
1
2
3
1
Country
1. Enter the four-digit password using the 4-way
button. The password is unit-specific.
2. Confirm the entry with the OK button.
3. Set the desired country setting.
NOTE: This option influences the country-specific
operating settings of the inverter. Please consult
KACO service for further information.
0
1
2
3
1
Grid type/
guideline
"
Select the grid type for the inverter’s installation
location.
AU, BG, FR,
GR, PT, ES,
CZ, KR
0
1
2
3
1
Switch-off volt.
The inverter is equipped with redundant 3-phase
monitoring. If the grid frequency exceeds or drops
below the configured values, the inverter switches off.
The minimum switch-off threshold can be set in 1 V
increments.
"
Configure the switch-off values for undervoltage
and overvoltage.
"
Where necessary, set period from occurrence of
the fault to shutdown of the inverter.
DE, AU, BG,
FR, GR, HU,
IL, PT, ES, CZ,
KR
0
1
2
3
1
Switch-off freq.
The inverter monitors the grid frequency continuously.
If the grid frequency exceeds or drops below the
configured values, the inverter switches off.
"
Set limit values for underfrequency and
overfrequency in 0.1 Hz increments.
"
Set period from occurrence of the fault to shutdown
of the inverter.
DE, BE, FR, IT,
AT, PL, UD
0
1
2
3
1
Overvoltage shutd.
"
Specify the shutdown threshold for fast and slow
overvoltage shutdown.
"
Set period from occurrence of the fault to shutdown
of the inverter.
DE, FR, GB,
HU, IL, IN, IT,
AT, PL, RU, ES,
TH, ZA, UD
"
Activate or deactivate password protection.
"
Specify the shutdown threshold for overvoltage
shutdown.
The 10-minute average for the measured voltage as
per EN50160 is used.
"
Set period from occurrence of the fault to shutdown
of the inverter.
BG, CZ, FR
0
1
2
3
1
Voltage drop
The voltage drop between the inverter and the feed-in
meter is added to the limit value that was set for grid
shutdown according to EN 50160. The limit value can be
set from 0 to 11 V in 1 V increments.
"
Specify the switch-off value for the voltage drop
(0 to 11 V).