A.5 Alarm Monitoring
A -7
A.5 Alarm Monitoring
Table A.5. Alarms
Name
# Register
Details
Alarm
IL jj 22
Servo Controller alarms are monitored using bit information.
b0: SVERR
Servopack Error
Servopack alarm detected. (For alarm details see IWjj24.)
b1: OTF
Positive Overtravel
Positive overtravel detected in the Servopack. (The P-OT signal is ON.)
b2: OTR
Negative Overtravel
Negative overtravel detected in the Servopack. (The N-OT signal is ON.)
b3: SOTF
Positive Software Limit
Movement detected beyond the positive software limit range.
b4: SOTR
Negative Software Limit
Movement detected beyond the negative software limit range.
b5: SVOFF
Servo Power OFF
A motion command was issued while the Servo power was OFF.
b6: TIMEOVER
Positioning Time Over
After completion of distribution, positioning was not completed within the
time specified in OWjj34 (Positioning Check Time).
b7: DISTOVER
Positioning Distance Over
Movement attempted which exceeds the positioning distance limit.
b8: FILTYPERR
Filter Type Error
Attempt was made to change the filter type before distribution was com-
pleted.
b9: FILTYMERR
Filter Time Error
Attempt was made to change the filter time before distribution was com-
pleted.
b10: MODERR
Control Mode Error
Position Control Mode motion commands were issued in a mode other than
Position Control Mode.
b11: SET_NRDY
Zero Point Not Set
The zero point has not been set.