beautypg.com

Ambient temperature, Main circuit terminal wiring – Yaskawa U1000 Industrial MATRIX Drive User Manual

Page 83

background image

n

Ambient Temperature

IP20/NEMA Type 1 Enclosure: -10 to +40 °C
IP00 Open Type Enclosure: -10 to +50 °C

n

Main Circuit Terminal Wiring

Yaskawa recommends using closed-loop crimp terminals on all drive models. Use only the tools recommended by the terminal

manufacturer for crimping.

Refer to Closed-Loop Crimp Terminal Recommendations on page 83

for closed-loop crimp

terminal recommendations.

Wire Gauges and Tightening Torques

Refer to Main Circuit Wire Gauges and Tightening Torque on page 24

.

Closed-Loop Crimp Terminal Recommendations

To maintain UL/cUL approval, UL Listed closed-loop crimp terminals are specifically required when wiring the drive main

circuit terminals on models 2o0068 to 2o0248 and 4o0052 to 4o0414. Use only the tools recommended by the terminal

manufacturer for crimping. Yaskawa recommends UL Listed crimp terminals made by JST and Tokyo DIP (or equivalent)

for the insulation cap.

Table i.28

matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp

terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge

and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department.
Wire gauge values shown in bold italic are the recommended values. Refer to local codes for proper selections.

Table i.28 Closed-Loop Crimp Terminal Size

Drive Model

Wire Gauge

(AWG, kcmil)

Screw

Size

Crimp Terminal

Model Number

Tool

Insulation Cap

Model No.

Code

<1>

R/L1, S/L2, T/L3

U/T1, V/T2, W/T3

Machine No.

Die Jaw

200 V Class

2o0028

10

M5

R5.5-5

YA-4

AD-900

TP-005

100-054-030

8

R8-5

AD-901

TP-008

100-054-032

2o0042

8

M6

R8-6

YA-4

AD-901

TP-008

100-065-184

6

R14-6

AD-902

TP-014

100-051-261

4

R22-6

YA-5

AD-953

TP-022

100-051-262

3

R22-6

2o0054

6

M6

R14-6

YA-5

AD-952

TP-014

100-051-261

4

R22-6

AD-953

TP-022

100-051-262

3

2o0068

4

M6

R22-6

YA-5

AD-953

TP-022

100-051-262

3

2o0081

6

M6

R14-6

YA-5

AD-952

TP-014

100-051-261

4

R22-6

AD-953

TP-022

100-051-262

3

2o0104

6

M8

R14-8

YA-4

AD-902

TP-014

100-054-035

4

R22-8

YA-5

AD-953

TP-022

100-051-263

3
2

R38-8

AD-954

TP-038

100-051-264

1

1/0

R60-8

AD-955

TP-060

100-051-265

2o0130

6

M8

R14-8

YA-5

AD-952

TP-014

100-054-035

4

R22-8

AD-953

TP-022

100-051-263

3
2

R38-8

AD-954

TP-038

100-051-264

1

1/0

R60-8

AD-955

TP-060

100-0051-265

i.9 Standards Compliance

YASKAWA ELECTRIC TOEP C710636 04C U1000 Industrial MATRIX Drive Quick Start Guide

83