Digital Operator Display

Fault Name

LF2

Output Current Imbalance
One or more of the phases in the output current are lost.

<4>

LSo

LSo Fault
Pull-out has been detected at low speed.

nSE

Node Setup Error
A terminal assigned to the node setup function closed during run.

oC

Overcurrent
Drive sensors detected an output current greater than the specified overcurrent level.

oFA00

Option Card Connection Error at Option Port CN5-A
Option compatibility error

oFA01

Option Card Fault at Option Port CN5-A
Option not properly connected

to

oFA02 to oFA06

Option Card Error Occurred at Option Port CN5-A

,

oFA10, oFA11

to

oFA12 to oFA17

Option Card Connection Error (CN5-A)

to

oFA30 to oFA43

Communication Option Card Connection Error (CN5-A)

oFb00

Option Card Fault at Option Port CN5-B
Option compatibility error

oFb01

Option Card Fault at Option Port CN5-B
Option not properly connected

oFb02

Option Card Fault at Option Port CN5-B
Same type of option card is currently connected

to

oFb03 to oFb11

Option card error occurred at Option Port CN5-B

to

oFb12 to oFb17

oFC00

Option Card Connection Error at Option Port CN5-C
Option compatibility error

oFC01

Option Card Fault at Option Port CN5-C
Option not properly connected

oFC02

Option Card Fault at Option Port CN5-C
Same type of option card is currently connected

to

oFC03 to oFC11

Option Card Error Occurred at Option Port CN5-C

to

oFC12 to oFC17

to

oFC50 to oFC55

Option Card Error Occurred at Option Port CN5-C

oH

Heatsink Overheat
The heatsink temperature exceeded the overheat pre-alarm level set to L8-02. The default value for L8-02

is determined by drive model selection (o2-04).

oH1

Overheat 1 (Heatsink Overheat)
The heatsink temperature exceeded the drive overheat level. Overheat level is determined by drive

capacity (o2-04).

oH3

Motor Overheat Alarm (PTC Input)
• The motor overheat signal to analog input terminal A1, A2, or A3 exceeded the alarm detection level.
• Detection requires setting multi-function analog inputs H3-02, H3-10, or H3-06 to E.

oH4

Motor Overheat Fault (PTC Input)
• The motor overheat signal to analog input terminal A1, A2, or A3 exceeded the fault detection level.
• Detection requires setting multi-function analog inputs H3-02, H3-10, or H3-06 to E.

oL1

Motor Overload
The electronic motor overload protection tripped

oL2

Drive Overload
The thermal sensor of the drive triggered overload protection.

i.6 Troubleshooting

68