Alarm detection – Yaskawa U1000 Industrial MATRIX Drive User Manual

Page 70

background image

<1> Displayed as CPF00 when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show

CPF01.

<2> Displayed as CPF20 when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show

CPF21.

<3> Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, Fdv, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.
<4> This function prevents continuous operation in reverse when using high frequency injection (n8-57 = 1) in AOLV/PM (A1-02 = 6) with a motor

for which no motor code has been entered (it does not only prevent reverse operation). Set L8-93, L8-94, and L8-95 to low values within range of
erroneous detection to quickly detect undesirable reverse operation.

u

Alarm Detection

n

Alarm Codes

An alarm is indicated by a code on the data display and the flashing ALM LED. The drive output is not necessarily switched

off.
To remove an alarm, trace and remove the cause, and reset the drive by pushing the Reset key on the operator or cycle the

power supply.
Refer to the Technical Manual for a complete list of causes and possible solutions.

Digital Operator Display

Alarm Name

AEr

Station Address Setting Error (CC-Link, CANopen, MECHATROLINK)
Option card node address is outside of the acceptable setting range.

AUv

Power Supply Undervoltage
The input power supply voltage became equal to or lower than the Input Power Supply Undervoltage

Detection Level (L2-21).

200 V Class: Approximately 150 Vrms

400 V Class: Approximately 300 Vrms

bb

Baseblock
Drive output interrupted as indicated by an external baseblock signal.

bUS

Option Communication Error
• The connection was lost after establishing initial communication.
• Only detected when the run command frequency reference is assigned to an option card.

CALL

Serial Communication Transmission Error
Communication has not yet been established.

CE

MEMOBUS/Modbus Communication Error
Control data was not received for the CE detection time set to H5-09.

CrST

Cannot Reset

CyC

MECHATROLINK Comm. Cycle Setting Error
Comm. Cycle Setting Error was detected.

dEv

Speed Deviation (for Control Mode with PG)
The deviation between the speed detection value for the pulse input and the speed reference after speed

agreement was reached exceeded the setting value of F1-10 for the time set in F1-11 or longer when the

Operation Selection at Deviation was set to continue operation (F1-04 = 3).

dnE

Drive Disabled

doH

Damping Resistor Overheat
The temperature of the built-in damping resistor exceeded the set value.

EF

Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for longer than 0.5 s.

EF0

Option Card External Fault
An external fault condition is present.

EF1

External Fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

External Fault (input terminal S2)
External fault at multi-function input terminal S2.

i.6 Troubleshooting

70

YASKAWA ELECTRIC TOEP C710636 04C U1000 Industrial MATRIX Drive Quick Start Guide