Fault Detection

n

Fault Displays

Digital Operator Display

Fault Name

Aov

Power Supply Overvoltage
The input power supply voltage became equal to or higher than the Input Power Supply Overvoltage

Detection Level.

200 V Class: Approximately 277 Vrms

400 V Class: Approximately 630 Vrms

AUv

Power Supply Undervoltage
The input power supply voltage became equal to or lower than the Input Power Supply Undervoltage

Detection Level (L2-21).

200 V Class: Approximately 150 Vrms

400 V Class: Approximately 300 Vrms

bUS

Option Communication Error
• The connection was lost after establishing initial communication.
• Only detected when the run command frequency reference is assigned to an option card.

CE

MEMOBUS/Modbus Communication Error
Control data was not received for the CE detection time set to H5-09.

CF

Control Fault
The torque limit was reached continuously for three seconds after the Stop command was input and

deceleration was not possible in OLV Control.

CoF

Current Offset Fault
Drive starts operation while the current-detection circuit failure, or the induced voltage remains in the

motor (coasting and after rapid deceleration).

to

,

,

,

to

,

to

,

to

,

to

<1> <2> <3>

CPF00 to CPF03,

CPF07, CPF08,

CPF11 to CPF14,

CPF16 to CPF24,

CPF26 to CPF35,

CPF40 to CPF45

Control Circuit Error

CPF06

Control Circuit Error
There is an error in the data saved to EEPROM.

CPF25

Terminal Board Not Connected

dEv

Speed Deviation (for Control Mode with PG)
The deviation between the speed detection value for the pulse input and the speed reference after speed

agreement was reached exceeded the setting value of F1-10 for the time set in F1-11 or longer when the

Operation Selection at Deviation was set to continue operation (F1-04 = 3).

doH

Damping Resistor Overheat
The temperature of the built-in damping resistor exceeded the set value.

dv1

Z Pulse Fault (CLV/PM control mode only)
The motor turned one full rotation without the Z Pulse being detected.

dv2

Z Pulse Noise Fault Detection (CLV/PM control mode only)
The Z Pulse is out of phase by more than 5 degrees for 10 consecutive revolutions.

dv3

Inversion Detection (CLV/PM control mode only)
The torque reference and acceleration are in opposite directions and the speed reference and actual motor

speed differ by more than 30% for the number of times set to F1-18.