Setting 2: Drive Dedicated Motor (Speed Range for Constant Torque: 1:10)
Use this setting when operating a drive duty motor that allows constant torque in a speed range of 1:10. The drive will allow
the motor to run with 100% load from 10% up to 100% speed. Running at slower speeds with full load can trigger an overload
fault.
Overload Tolerance
Cooling Ability
Overload Characteristics
A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below
Rated Speed=100% Speed
60 s
Continuous
A
B
C
Speed (%)
Torque (%)
100
150
110
100120 167 200
55
50
0
Motor is designed to effectively cool
itself even at low speeds.
Continuous operation with 100% load
from 6 Hz to E1-06, Motor Base
Frequency.
Setting 3: Vector Motor (Speed Range for Constant Torque: 1:100)
Use this setting when operating a drive-dedicated motor that allows constant torque in a speed range of 1:100. This motor type
is allowed to run with 100% load from 1% up to 100% speed. Running slower speeds with full load can trigger an overload
fault.
Overload Tolerance
Cooling Ability
Overload Characteristics
A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below
150
100
90
50
0 1
100120 167 200
A
B
C
Continuous
Speed (%)
Rated Speed=100% Speed
Torque (%)
60 s
Motor is designed to effectively cool
itself at speeds near 0.6 Hz.
Continuous operation with 100% load
from 0.6 Hz to E1-06, Motor Base
Frequency.
Continuous operation below 0.6 Hz
may cause an oL1 or oL2 fault.
Setting 4: PM Derated Torque Motor
Use this setting when operating a PM motor. PM motors for derated torque have a self-cooling design and the overload tolerance
drops as the motor slows. Electronic thermal overload is triggered in accordance with the motor overload characteristics,
providing overheat protection across the entire speed range.
Overload Tolerance
Cooling Ability
Overload Characteristics
Continuous
60 s
Motor Speed (%)
Torque (%)
150
10
33
100
120
100
80
50
0.0
Motor is designed to produce 100%
torque at base speed. Built with
effective cooling capabilities.
Reaching 100% when operating at
below the base frequency causes a
motor overload fault (oL1). The drive
fault output closes and the motor coasts
to stop.
Setting 5: Constant Torque PM Motors (Constant Torque Range of 1:500)
Sets necessary protection characteristics when driving a PM with constant torque. These motors allow for a speed control from
0.2% to 100% when operating with 100% load. Slower speeds with 100% load will trigger overload.