Digital Operator Display

Error Name

Er-11

Motor Speed Error

Er-12

Current Detection Error

Er-13

Leakage Inductance Error

Er-14

Motor Speed Error 2

Er-15

Torque Saturation Error

Er-16

Inertia ID Error

Er-17

Reverse Prohibited Error

Er-18

Induction Voltage Error

Er-19

PM Inductance Error

Er-20

Stator Resistance Error

Er-21

Z Pulse Correction Error

Er-25

High Frequency Injection Parameter Tuning Error

u

Fault Reset Methods

When a fault occurs, the cause of the fault must be removed and the drive must be restarted. The table below lists the different

ways to restart the drive.

After the Fault Occurs

Procedure

Fix the cause of the fault, restart the drive, and

reset the fault

Press

on the digital operator when the error code

is displayed.

LO

RE

F2

F1

ESC

RUN

STOP

ENTER

RESET

RESET

- MODE -

oC

Overcurrent

DRV

FWD

RESET

ALM

Resetting via Fault Reset Digital Input S4

Close then open the fault signal digital input via

terminal S4. S4 is set for “Fault Reset” as default

(H1-04 = 14).

Fault Reset Switch

Drive

S4 Fault Reset Digital Input

SC Digital Input Common

Turn off the main power supply if the above methods do not reset the fault. Reapply power after the

digital operator display has turned off.

ON

OFF

2

1

Note:

If the Run command is present, the drive will disregard any attempts to reset the fault. Remove the Run command before attempting to clear

a fault situation.

i.6 Troubleshooting

74

YASKAWA ELECTRIC TOEP C710636 04C U1000 Industrial MATRIX Drive Quick Start Guide