Digital Operator Display

Alarm Name

EF3

External Fault (input terminal S3)
External fault at multi-function input terminal S3.

EF4

External Fault (input terminal S4)
External fault at multi-function input terminal S4.

EF5

External Fault (input terminal S5)
External fault at multi-function input terminal S5.

EF6

External Fault (input terminal S6)
External fault at multi-function input terminal S6.

EF7

External Fault (input terminal S7)
External fault at multi-function input terminal S7.

EF8

External Fault (input terminal S8)
External fault at multi-function input terminal S8.

FbH

Excessive PID Feedback
PID feedback input is greater than the level set to b5-36 for longer than the time set to b5-37. Set b5-12

to 2 or 5 to enable fault detection.

FbL

PID Feedback Loss
PID feedback loss detection is programmed to trigger a fault (b5-12 = 2 or 5) and the PID feedback level

is below the detection level set to b5-13 for longer than the time set to b5-14.

Fdv

Power Supply Frequency Fault
The input power supply frequency exceeded the allowable frequency fluctuation.

Hbb

Safe Disable Signal Input
Both Safe Disable Input channels are open.

HbbF

Safe Disable Signal Input
One Safe Disable channel is open while the other channel is closed.

HCA

Current Alarm
Drive current exceeded overcurrent warning level (150% of the rated current).

LT-1

Cooling Fan Maintenance Time
The cooling fan has reached its expected maintenance period and may need to be replaced.

Note:

An alarm output (H2-oo = 10) will only be triggered if both (H2-oo = 2F and

H2-oo = 10) are set.

LT-2

Capacitor Maintenance Time

The main circuit and control circuit capacitors are nearing the end of their expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

LT-3

Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

oH

Heatsink Overheat
The heatsink temperature exceeded the overheat pre-alarm level set to L8-02. The default value for L8-02

is determined by drive model selection (o2-04).

oH2

Heatsink Overheat Warning
“Heatsink Overheat Warning” was input to a multi-function input terminal, S1 through S8 (H1-oo= B).

oH3

Motor Overheat Alarm (PTC Input)
• The motor overheat signal to analog input terminal A1, A2, or A3 exceeded the alarm detection level.
• Detection requires setting multi-function analog inputs H3-02, H3-10, or H3-06 to E.

oL3

Overtorque Detection 1
The current has exceeded the value set for Torque Detection Level 1 (L6-02) for longer than the allowable

time (L6-03).

oL4

Overtorque Detection 2
The current has exceeded the value set for Torque Detection Level 2 (L6-05) for longer than the allowable

time (L6-06).

i.6 Troubleshooting

YASKAWA ELECTRIC TOEP C710636 04C U1000 Industrial MATRIX Drive Quick Start Guide