i.4

Electrical Installation

u

Standard Connection Diagram

Connect the drive and peripheral devices as shown in

Figure i.12

. It is possible to set and run the drive via the digital operator

without connecting digital I/O wiring.

NOTICE: Inadequate wiring could result in damage to the drive. Install adequate branch circuit protection per applicable codes. The drive

is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 240 Vac maximum (200 V class),

480 Vac maximum (400 V class: 4E

oooo and 4Woooo), and 500 Vac maximum (400 V class: 4Aoooo and 4Poooo) when

protected by branch circuit protection devices specified in this document.

NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.

NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to

comply may result in abnormal operation of drive and nearby equipment.

NOTICE: Correctly set Sink/Source jumper S3 for internal power supply. Failure to comply may result in damage to the drive.

Note:

The minimum load for the relay outputs M1-M2, M3-M4, M5-M6, and MA-MB-MC is 10 mA.

i.4 Electrical Installation

20