Output terminals, Serial communication terminals – Yaskawa U1000 Industrial MATRIX Drive User Manual

Page 31

background image

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Analog Inputs /

Pulse Train

Input

RP

Multi-function pulse train input

(Frequency reference)

• Input frequency range: 0 to 32 kHz
• Signal Duty Cycle: 30 to 70%
• High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc
• Input impedance: 3 kΩ

+V

Power supply for analog inputs

10.5 Vdc (max allowable current 20 mA)

-V

Power supply for analog inputs

-10.5 Vdc (max allowable current 20 mA)

A1

Multi-function analog input 1

(Frequency reference bias)

-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)

A2

Multi-function analog input 2

(Frequency reference bias)

• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by DIP switch S1 and H3-09.

A3

Multi-function analog input 3

(Auxiliary frequency reference)/PTC Input

• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• Use DIP switch S4 on the terminal board to select between analog and

PTC input.

AC

Frequency reference common

0 V

E (G) Ground for shielded lines and option cards

n

Output Terminals

Table i.8

lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.

Table i.8 Control Circuit Output Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Fault Relay

Output

MA

N.O. output (Fault)

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

MB

N.C. output (Fault)

MC

Fault output common

Multi-Function
Digital Output

<1>

M1

Multi-function digital output (During run)

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

M2
M3

Multi-function digital output (Zero speed)

M4
M5

Multi-function digital output (Speed Agree 1)

M6

Monitor Output

MP

Pulse train output (Output frequency)

32 kHz (max)

FM

Analog monitor output 1 (Output frequency)

-10 to +10 Vdc, 0 to +10 Vdc, or 4 to 20 mA

AM

Analog monitor output 2 (Output current)

AC

Monitor common

0 V

Safety Monitor

Output

DM+ Safety monitor output

Outputs status of Safe Disable function. Closed when both Safe

Disable channels are closed. Up to +48 Vdc 50 mA

DM- Safety monitor output

External Power

Supply

24V

External power supply

24 V (Max. 150 mA)

<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life. Switching

life is estimated at 200,000 times (assumes 1 A, resistive load).

n

Serial Communication Terminals

Table i.9 Control Circuit Terminals: Serial Communications

Type

No.

Signal Name

Function (Signal Level)

MEMOBUS/Modbus
Communication

<1>

R+

Communications input (+)

MEMOBUS/Modbus communication: Use an

RS-422 or RS-485 cable to connect the drive.

RS-422/RS-485

MEMOBUS/Modbus

communication

protocol

115.2 kbps (max.)

R-

Communications input (-)

S+

Communications output (+)

S-

Communications output (-)

IG

Shield ground

0 V

<1> Enable the termination resistor in the last drive in a MEMOBUS/Modbus network by setting DIP switch S2 to the ON position. Refer to the manual

section on Control I/O Connections for more information.

i.4 Electrical Installation

YASKAWA ELECTRIC TOEP C710636 04C U1000 Industrial MATRIX Drive Quick Start Guide