Terminal A2 Input Signal Selection

Terminal A2 can be used to input either a voltage or a current signal. Select the signal type using switch S1 as explained in

Table i.13

. Set parameter H3-09 accordingly as shown in

Table i.14

.

Note:

If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency

reference.

Table i.13 DIP Switch S1 Settings

Setting

Description

V (left position)

Voltage input (-10 to +10 V or 0 to 10 V)

I (right position)

Current input (4 to 20 mA or 0 to 20 mA): default setting

Table i.14 Parameter H3-09 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H3-09

Terminal A2 signal level selection

Selects the signal level for terminal A2.

0: 0 to 10 Vdc

1: -10 to 10 Vdc

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

2

u

Terminal A3 Analog/PTC Input Selection

Terminal A3 can be configured either as multi-function analog input or as PTC input for motor thermal overload protection.

Use switch S4 to select the input function as described in

Table i.15

.

Table i.15 DIP Switch S4 Settings

Setting

Description

AI (lower position) (default)

Analog input for the function selected in parameter H3-06

PTC (upper position)

PTC input. Parameter H3-06 must be set to E (PTC input)

u

Terminal AM/FM Signal Selection

The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board

as explained in

Table i.16

. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.

The default selection is voltage output for both terminals.

Table i.16 Jumper S5 Settings

Terminal

Voltage Output

Current Output

Terminal AM

AM

FM

V

I

AM

FM

V

I

Terminal FM

AM

FM

V

I

AM

FM

V

I