13.3 Protective Devices

* optional

13.4 Licences

* C 10/11: Only possible if the 3-phase nominal voltage of the phase conductor is 400 V
** EN 50438: Does not apply to all country standard deviations of EN 50438.
*** NRS 97-2-1: This standard stipulates that a special sticker be attached to the AC distribution to draw attention to the AC-side

disconnection of the inverter in case of grid failure (for more details, see NRS 97-2-1, Sec. 4.2.7.1 and 4.2.7.2)

DC reverse polarity protection

Short-circuit diode

Protection against module reverse currents

Diode

Input-side load disconnect unit*

DC switch-disconnector

Utilisation category of the DC switch-
disconnector*

DC-21B

DC overvoltage protection

Thermally monitored varistors

AC short-circuit current capability

Current control

Grid monitoring

SMA Grid Guard 4

Maximum permissible fuse protection

50.0 A

Earth fault monitoring

Insulation monitoring R

iso

> 200 k Ω

All-pole sensitive residual-current monitoring unit

available

Country standards,
as of 06/12

STP

15000TLEE-10

STP

15000TLHE-10

STP

20000TLEE-10

STP

20000TLHE-10

VDE-AR-N4105

VDE 0126-1-1

AS4777

C10/11*

PPDS

UTE C15-712-1

PPC

EN50438**

RD1699/2000

RD661/2007

IEC 61727

G59/2

CEI 0-21

NRS 97-2-1***

BDEW 2008