SMA STP 15000TL Installation User Manual
Page 78
Troubleshooting
SMA Solar Technology AG
78
STP20TLHE-IA-IEN122222
Installation Manual
4. Remove all varistors.
If you have not received an insertion tool for
operating the terminals with your replacement
varistors, contact SMA Solar Technology AG.
5. Use a multimeter to check all the varistors to see if
there is a conductive connection between
connectors 2 and 3.
Result
Measure
☑ There is a conductive
connection.
The varistor is functional. Presumably there is a different error in the
inverter.
• Proceed to step 8.
• Contact the SMA Service Line (see Section 15 "Contact"
☑ There is no conductive
connection.
The respective varistor is defective and must be replaced.
Varistor failure is due to influences which affect all varistors
similarly (temperature, age, induced overvoltages).
SMA Solar Technology AG recommends replacing all varistors.
The varistors are specially manufactured for use in the inverter and
are not commercially available. You must order replacement
varistors directly from SMA Solar Technology AG (see Section 14
"Accessories" (page 93)). Only use original varistors that are sold
by SMA Solar Technology AG.
• To replace the varistors, proceed to step 6.