SMA STP 15000TL Installation User Manual
Page 69
SMA Solar Technology AG
Messages
Installation Manual
STP20TLHE-IA-IEN122222
69
301
< Grid fault >
The 10-minute average line voltage is no
longer within the permissible range.
This can be caused by one of the
following:
• The line voltage at the termination
point of the inverter is too high.
• The grid impedance at the
termination point of the inverter is
too high.
The inverter disconnects from the grid to
maintain power quality.
• Check the line voltage at the
termination point of the inverter:
If, due to local grid conditions, the line
voltage exceeds the configured limiting
value, ask the network operator whether the
voltage can be adjusted at the feed-in point,
or whether it would be acceptable to modify
the limiting value for power quality
monitoring.
If the line voltage is continually within the
tolerance range, and this error is still
displayed, contact the SMA Service Line.
401 …
404
< Grid fault >
The inverter is no longer in grid-parallel
operation and has stopped feed-in for
safety reasons.
• Check the grid connection for strong,
short-term frequency variations.
501
< Grid fault >
The power frequency is not within the
permissible range. The inverter
disconnects from the electricity grid for
safety reasons.
• If possible, check the power frequency
and observe how often major
deviations occur.
If there are frequent fluctuations and this error
occurs as a result, ask your network operator
if it would be acceptable to change the
operating parameters.
Discuss the proposed parameters with the
SMA Service Line.
601
< Grid fault >
The internal monitoring function of the
inverter has detected an excessively high
proportion of direct current in the line
current.
• Check the grid connection for direct
current.
• If this event occurs often, check with the
network operator whether it is possible
to raise the limiting value for
monitoring.
701
< Frequency not permitted >
< Check parameter >
The power frequency is outside the
permissible range. The inverter
disconnects from the electricity grid for
safety reasons.
• As far as possible, check the power
frequency and observe how often
major fluctuations occur.
If there are frequent fluctuations and this error
occurs as a result, ask your network operator
if it would be acceptable to change the
operating parameters.
Discuss the proposed parameters with the
SMA Service Line.
Event no. Display message and cause
Corrective measures