Disconnecting the Inverter from Voltage Sources

SMA Solar Technology AG

60

STP20TLHE-IA-IEN122222

Installation Manual

9. Ensure that L1, L2 and L3 are disconnected from

voltage sources to PE.

10. If a multi-function relay is installed in the inverter,

ensure that it is disconnected from all voltage
sources as follows:
– Release the screw of the display and flip the

display up until it clicks into place.

– Ensure that all terminals of the multi-function relay

are disconnected from voltage sources to PE.

☑ The inverter is now dead and work can be carried out.

DANGER!
Danger to life due to high voltages in the inverter
Death due to electric shock

There is residual voltage in the inverter.

• Wait 20 minutes before opening the upper enclosure lid.
• Do not open the DC lid.

PE