7105

< Param. setting failed >

• Check the parameters of the SD card

for valid values.

• Ensure change rights via SMA Grid

Guard code.

7106

< Update file defect. >

• Re-format the SD card.
• Re-save the files to the SD card.

7110

< No update file found >

• Copy the update file into the SD card

drive :\UPDATE directory.

7201 …
7202

< Data stor. not poss. >
An internal device fault that does not
prevent the inverter from feeding power
to the grid.

• If this fault occurs often, contact the

SMA Service Line (see Section 15
"Contact" (page 94)).

7303

< Update main CPU failed >
Internal device fault.

• Contact the SMA Service Line

(see Section 15 "Contact" (page 94)).

7305

< Update RS485I module failed >
An internal device fault that does not
prevent the inverter from feeding power
to the grid.

• Re-try update.
• If this fault occurs again, contact the

SMA Service Line (see Section 15
"Contact" (page 94)).

7307

< Update Bluetooth failed >
An internal device fault that does not
prevent the inverter from feeding power
to the grid.

• Re-try update.
• If this fault occurs again, contact the

SMA Service Line (see Section 15
"Contact" (page 94)).

7311

< Update language table failed >
An internal device fault that does not
prevent the inverter from feeding power
to the grid.

• Re-try update.
• If this fault occurs again, contact the

SMA Service Line (see Section 15
"Contact" (page 94)).

7401

< Varistor defective >
At least one of the thermally monitored
varistors is defective.

• Check the varistors as described in

Section 11.2 "Checking the Function of
the Varistors" (page 77)
.

7702 …
7703

< Self diagnosis > or
< Interference device >

• Contact the SMA Service Line

(see Section 15 "Contact" (page 94)).

8001

< Derating occurred >
The power supplied by the inverter has
been reduced to below the nominal
power for more than 10 minutes due to
excessive temperature.

If this event occurs frequently:

• Ensure sufficient ventilation.
• Check heat dissipation, as described in

Section 9.2 "Checking Heat
Dissipation" (page 61).

Event no. Display message and cause

Corrective measures