beautypg.com

SMA STP 15000TL Installation User Manual

Page 74

background image

Messages

SMA Solar Technology AG

74

STP20TLHE-IA-IEN122222

Installation Manual

8801 …
8803

The display is blank. The inverter
continues feeding into the electricity grid.
This error can have the following causes:

• The ambient temperature is so low

that the display disconnects to
protect itself.

• The inverter cannot identify the

display type.

• No display is connected or the

connection is defective.

• Wait until the temperature has risen

above ‒25°C.

• Contact the SMA Service Line

(see Section 15 "Contact" (page 94)).

9002

< Inst. code invalid >
The SMA Grid Guard code entered
(personal installer password) is not valid.

• Enter a valid SMA Grid Guard code.

9003

< Grid param. locked >
The current country data set is locked.

• Enter a valid SMA Grid Guard code

for changing the country data set.

9005

< Changing grid param. not possible >
< Ensure DC supply >

• DC voltage at the DC input is not

sufficient to run the main CPU.

• The selected rotary switch setting

for the language settings is not
programmed.

• The parameters to be changed are

protected.

• Make sure that there is sufficient DC

voltage available (green LED is
glowing or flashing).

• Check the setting of the rotary switches

(see Section 5.4.2).

• Enter the SMA Grid Guard code.

9007

< Abort self-test >
There is either an error in the AC
installation or the set voltage and
frequency limits do not comply with the
requirements of the Italian electricity
grids.

• Check AC installation.
• Adjust the connection as described in

Section 6.3 "Connection to the
Electricity Grid (AC)" (page 29).

• Check for correct country settings as

described in Section 6.5 "Setting the
Country Data Set and Display
Language" (page 42).
The self-test is only required for
installations in Italy.

Event no. Display message and cause

Corrective measures