2 sunny tripower 15000tl high efficiency, Sunny tripower 15000tl high efficiency – SMA STP 15000TL Installation User Manual
Page 86
Technical Data
SMA Solar Technology AG
86
STP20TLHE-IA-IEN122222
Installation Manual
* Depending on country setting
Efficiency
13.1.2 Sunny Tripower 15000TL High Efficiency
DC Input
* The maximum open-circuit voltage which can occur at a cell temperature of − 10°C must not exceed the maximum input voltage.
AC Output
Overvoltage category as per IEC 60664-1
III
Maximum efficiency, η
max
98.5%
European weighted efficiency, η
EU
98.3%
Maximum DC power at cos φ = 1
15,200 W
Maximum input voltage*
1,000 V
MPP voltage range at 230 V AC
580 V … 800 V
Rated input voltage
580 V
Minimum input voltage at 230 V AC
570 V
Start input voltage
620 V
Maximum input current
36 A
Maximum input current per string
36 A
Number of independent MPP inputs
1
Strings per MPP input
6
Rated power at 230 V, 50 Hz
15,000 W
Maximum apparent AC power
15,000 VA
Rated grid voltage
3/N/PE, 230 V/400 V
AC voltage range*
160 V … 280 V
Nominal AC current at 230 V
21.7 A
Maximum output current
24.0 A
Maximum short-circuit current
50 A
Total harmonic factor of the output current with
total harmonic factor of the AC voltage < 2%,
AC power > 0.5 rated power
≤ 2.6%
Maximum residual output current
96 mA
Rated power frequency
50 Hz
AC power frequency*
50 Hz/60 Hz
Operating range at AC power frequency 50 Hz
44 Hz … 55 Hz
Operating range at AC power frequency 60 Hz
54 Hz … 65 Hz