Messages

SMA Solar Technology AG

70

STP20TLHE-IA-IEN122222

Installation Manual

1302

< Waiting for grid voltage > or
< Installation failure grid connection >
< Check grid and fuses >
The inverter has detected an error in the
AC cabling and cannot connect to the
electricity grid. The reason for this could
be an incorrect country setting.

• Check AC installation
• Adjust the connection as described in

Section 6.3 "Connection to the
Electricity Grid (AC)" (page 29).

• Check that the country setting is correct:

– Via the rotary switch: see Section

6.5.1 "Checking the Country Data
Set" (page 44)
.

– Via communication: setting the

parameter "CntrySet" or "Set
country standard"

1501

< Reconnection fault grid >
The measured voltage or frequency is
too high or too low for connection to the
electricity grid.
Possibly, a changed country data set or
changed parameters do not correspond
to the local requirements for connecting
to the electricity grid.

• Check that the country setting is correct:

– Via the rotary switch: see Section

6.5.1 "Checking the Country Data
Set" (page 44)
.

– Via communication: setting the

parameter "CntrySet" or "Set
country standard"

• Check whether the voltage and

frequency of the electricity grid are
within the limits of the configured
country data set.

• If individual parameters within a

country data set have been changed,
re-select the original country data set
for the installation country.

3301 …
3303

< Unstable operation >
There is not enough power at the DC
input of the inverter for stable operation.
This may be caused by snow on the PV
modules.

• Wait for more irradiation.
• If this event recurs at medium

irradiation, check the PV plant design
and correct the circuitry of the PV array.

Event no. Display message and cause

Corrective measures