Technical Data

Installation Manual

STP20TLHE-IA-IEN122222

89

* Depending on country setting

Efficiency

13.2 General Data

* optional

Rated power frequency

50 Hz

AC power frequency*

50 Hz/60 Hz

Operating range at AC power frequency 50 Hz

44 Hz … 55 Hz

Operating range at AC power frequency 60 Hz

54 Hz … 65 Hz

Displacement power factor, adjustable

0.8

overexcited

… 0.8

underexcited

Feed-in phases

3

Connection phases

3

Overvoltage category as per IEC 60664-1

III

Maximum efficiency, η

max

99.0%

European weighted efficiency, η

EU

98.7%

Width x height x depth, with handle of DC switch-
disconnector*

665 mm x 680 mm x 265 mm

Weight

45 kg

Length x width x height of packaging

780 mm x 380 mm x 790 mm

Transport weight

53 kg

Climatic category (according to IEC 60721-3-4)

4K4H

Operating temperature range

− 25°C … +60°C

Maximum permissible value for relative humidity, non-
condensing

100%

Maximum operating altitude above Mean Sea Level

3,000 m

Noise emission (typical)

≤ 40 dB(A)

Power loss in night operation

< 1 W

Topology

Transformerless

Cooling concept

OptiCool: temperature-controlled fan

Fan connection

Designed for safe disconnection in

accordance with DIN EN 62109-1

Protection rating according to IEC 60529

IP65

Protection class (according to IEC 62103)

I

Strain relief category of the cable glands according to
EN 50262

A

This manual is related to the following products: