Electrical Connection

Installation Manual

STP20TLHE-IA-IEN122222

49

6.5.3 Setting the country data set and language using rotary

switches

1. Disconnect the inverter (see Section 8 "Disconnecting the Inverter from Voltage Sources"

(page 58)).

2. Set the rotary switches A and B with a screwdriver

(blade width: 2.5 mm) to the desired position
(see table in Section 6.5.1 "Checking the Country
Data Set" (page 44)).

3. Commission the inverter (see Section 7 "Commissioning" (page 55)).

DANGER!
Danger to life due to high voltages in the event of electricity grid failure

If you set the inverter to "Off-Grid50/Island mode 50 Hz" or "Off-Grid60/Island mode
60 Hz", you may not operate the inverter on the electricity grid, but only on the stand-alone
grid, because the inverter does not then satisfy any country-specific standards or directives.
If there is an electricity grid failure, this prevents danger of backfeed.

• If the inverter is set to "Off-Grid50/Island mode 50 Hz" or "Off-Grid60/Island mode

60 Hz", never operate the inverter directly on the electricity grid.

Temporarily setting the display language
to English

• To set the display language to English,

push the left switch 1 up until it locks into
place. Use an object with a small tip, e.g.
a ballpoint pen to do this.

• To reset the display language back to

the original language, push the left
switch 1 down until it locks into place.
Use an object with a small tip, e.g. a
ballpoint pen to do this.