beautypg.com

Temperature, Humidity, Altitude – H3C Technologies H3C SR6600-X User Manual

Page 14: Cleanness

background image

4

Temperature

To ensure normal operation of the router, make sure the room temperature meets the requirements

in

Table 1

.

Table 1 Temperature requirements

Item

Temperature

Operating temperature

0°C to 45°C (32°F to 113°F)

Storage temperature

–40°C to +70°C (–40°F to +158°F)

Humidity

Maintain appropriate humidity in your equipment room, as described in

Table 2

.

Lasting high relative humidity tends to cause poor insulation, electricity creepage, mechanical
property change of materials, and corrosion of metal parts.

Lasting low relative humidity is likely to result in loose screws due to washer contraction, and even
ESD, which causes the circuits to fail.

Table 2 Humidity requirements

Item Humidity

Operating humidity (noncondensing)

10% to 95%

Storage humidity (noncondensing)

5% to 95%

Altitude

Table 3 Altitude requirements

Item Altitude

Operating altitude

–60 m (–196.85 ft) to 4 km (2.49 miles)

Storage altitude

–60 m (–196.85 ft) to 4.5 km (2.80 miles)

Cleanness

Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of metal

components and contact points, especially when indoor relative humidity is low. In the worst case,
electrostatic adsorption can cause communication failure.

Table 4 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/m

3

)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)