Cooling system, Esd prevention – H3C Technologies H3C SR6600 User Manual

Page 12

background image

4

Table 4 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/cu m)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

NOTE:

Dust particle diameter ≥ 5 μm

The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and

premature aging of components, as shown in

Table 5

.

Table 5 Harmful gas limits in an equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01

Cooling system

The H3C SR6602 router adopts left to right airflow for heat dissipation.

Figure 3 SR6602 airflow

Make sure there is enough space (greater than 10 cm (3.94 in)) around the air intake and outlet
vents on the router for good ventilation.

Make sure the installation site has a good cooling system.

ESD prevention

To prevent electrostatic discharge (ESD), note the following guidelines:

Make sure that the router and the floor are well grounded.

Take dust-proof measures for the equipment room.

Maintain the humidity and temperature at a proper level.

Always wear an ESD-preventive wrist strap when touching a circuit board or transceiver module.

Place the removed memory module, CF card, or HIM/MIM on an antistatic workbench, with the
face upward, or put it into an antistatic bag.