Install a dust plug on the transceiver module to avoid damage to the transceiver module.

Examining the installation site

The H3C SR6602 router can only be used indoors. To ensure that the router works properly and to
prolong its service lifetime, the installation site must meet the following requirements:

Temperature and humidity

Cleanness

EMI

Temperature and humidity

You must maintain a proper temperature and humidity in the equipment room. Long-term high humidity

may lead to bad insulation, electricity leakage, mechanical property changes, and metal corrosion.

However, if the relative humidity is too low, captive screws may become loose as the result of contraction

of insulation washers and static electricity may be produced in a dry environment to jeopardize the

circuits on the device. A high temperature is the most undesirable condition, because it accelerates the
aging of insulation materials and significantly lowers reliability and service life of the router.
For the temperature and humidity requirements of the router, see

Table 1

and

Table 2

.

Table 1 Temperature requirements

Item

Temperature

Operating Temperature

0°C to 45°C (32°F to 113°F)

Storage Temperature

-40°C to 70°C(-40°F to 158°F)

Table 2 humidity requirements

Item Humidity

Operating humidity

10% to 95%

Storage humidity

5% to 95%

Altitude

Table 3 Altitude requirements

Item Altitude

Operating altitude

–60 m (–196.85 ft) to 3 km (1.86 miles)

Storage altitude

–60 m (–196.85 ft) to 4.5km(2.8 miles)

Cleanness

Dust buildup on the chassis may result in electrostatic adsorption, which causes poor contact of metal

components and contact points, especially when indoor relative humidity is low. In the worst case,

electrostatic adsorption can cause communication failure.