Programming contact closures – Wavetronix SmartSensor Advance Extended Range (SS-200E) - User Guide User Manual
Page 130
In this chapter
˽ Click 112/114 Contact Closure Cards
˽ Click 172/174 Contact Closure Cards
˽ Click 104 DIN Rail Module
12
Once the sensor has been installed and configured, the detections will be recorded in a
controller through the use of contact closure modules. The Click 112/114 and 172/174 cards
are specifically designed to easily integrate the SmartSensor Advance with existing NEMA
TS1, TS2, 170 and 2070 controllers.
Click 112/114 Contact Closure Cards
You can use SmartSensor Advance and SmartSensor Advance Extended Range with the
Click 112/114 contact closure cards using the Z4 protocol. Communication from the sensor
can be set up by the cards or by using SmartSensor Manager.
To connect and autobaud to the detector rack cards:
1 Connect from the Click 222 RS-485 A port to a bus 1 port on the appropriate rack card.
Connect from the Click 222 RS-485 B port to a bus 1 port on another rack card.
2 If you are using Click 112 cards, use a patch cord to share bus 1 between cards dedi-
cated to the same sensor. If you have more than two sensors in your system, repeat
steps 1–3 to connect bus 1 for all remaining rack cards.
3 Connect from a Click 222 bridge port to bus 2 of the rack cards.
4 Daisy-chain between the bus 2 ports of all of the rack cards for device configuration.
5 Verify that detections are registering on the Channel LEDs.
Programming Contact Closures
12