Table 3-22 – Verilink DPRI 2922 (880-503142-001) Product Manual User Manual

Page 66

background image

Configuring the DPRI 2922 Via the NCM 2000 Craft Interface

3-36

Verilink DPRI 2922

Table 3-22

Net Port Alarm Threshold Configuration Menu Commands

Command

Description

Options

Pn

Alarm Reporting (NET): Enabling alarm reporting conveys any messages

indicating alarms for each network port. These alarms are declared to both the

ASCII interface as well as the Node Manager, if used. If this option is set to No,

even if alarm reports for individual ports are requested, they are not reported.

The LEDs remain amber or red in an alarm condition. Set this option to No

while configuring the node; then set to Yes for normal operation.

For any of the Advanced Automatic Protection Switching features—dial backup

or other backup options—this parameter MUST be set to Yes.

Yes or No

(Y/N)

Dn

Alarm Reporting (DATA): Enabling alarm reporting conveys any messages

indicating alarms for each data port. These alarms are declared to both the

ASCII interface as well as the Node Manager, if used. If this option is set to No,

even if alarm reports for individual ports are requested, they are not reported.

The LEDs remain amber or red in an alarm condition. Set this option to No

while configuring the node; then set to Yes for normal operation.

For any of the Advanced Automatic Protection Switching features—dial backup

or other backup options—this parameter MUST be set to Yes.

Yes or No

(Y/N)

Fn

Loss-of-Frame (LOF) Threshold/LOF Interval: Use this option to indicate an

interval that is greater than the threshold.

Threshold:

1—86400

0 to disable

Interval:

3—86400

seconds

Ln

Loss of Signal (LOS) Threshold/LOS Interval: Use this option to indicate an

interval that is greater than the threshold.

If LOS occurs, troubleshoot this situation first and ignore all other alarms

(There will be other alarms). This is the most severe alarm.

Threshold:

1—86400

0 to disable

Interval:

3—86400

seconds

Rn

Remote Alarm Indication (RAI) Threshold/RAI Interval:

In SF, an RAI consists of Bit 2 of all 24 channels set to zero.

In ESF, an RAI is a repeating pattern of eight Ones followed by eight Zeros

transmitted over the ESF Data Link.

Threshold:

1—86400

0 to disable

Interval:

1—86400

seconds

An

Alarm Indication Signal (AIS) Threshold/AIS Interval:

Threshold:

1—86400

0 to disable

Interval:

1— 86400

seconds

Bn

Bipolar Violation (BPV) Threshold/BPV Interval:

Threshold:

1—86400

0 to disable

Interval:

1—86400

seconds