beautypg.com

3 date, Date, Figure 4.9 – RLE FDS-Wi V.2.5 User Manual

Page 55: Date section, Table 4.5, Date section options

background image

www.rletech.com

55

970.484.6510

4

Web Interface – Integration Version

4.2.3 Date

The Date section allows users to set the current date and time for the system and displays the

first three letters of the day of the week.

Figure 4.9 Date Section

TCP Max Seg Size

The Wireless Gateway is defaulted to 1436 packet size for web

page data. Users may select 536 for limited bandwidth or VPN

applications.

Web User Name

If this field is left blank, the Wireless Gateway’s default user name

is fds (all lower case). Users can enter a user name up to 18

characters, either alpha, numeric, or a combination of the two. The

Wireless Gateway user name is case sensitive.

Web Password Read

Only

Two separate passwords can be established on the Wireless

Gateway.

The Read Only password allows users to access the Wireless

Gateway Web interface and view the conditions of the sensors, but

does not allow users to make changes to the Wireless Gateway

configuration.

Web Password

Read/Write

The second configurable password on the Wireless Gateway

provides users with expanded access.

The Read/Write password allows users to view the condition of the

sensors and make changes to the Wireless Gateway configuration.

Web Refresh Rate

The Web Refresh Rate is the amount of time the system waits until

it updates the Web interface with current data. To change the rate,

click in the field and type in the desired amount of time (in seconds).

The minimum recommended refresh rate is five seconds;

otherwise, errors may occur that prevent the system from

functioning properly.

The default refresh rate is set to 0 - the Wireless Gateway will not

refresh at all. Users must set a refresh rate in order for the system

to automatically update.

Option

Description

Date

Enter the date in mm/dd/yy format.

Time

Entered the current time in hh:mm:ss format, where the hour is a

two digit number between 01 and 24.

Table 4.5 Date Section Options

Option

Description

Table 4.4 Network and Web Section Options (continued)