NOTE When the desired edits have been made, click the Submit Changes button to save

the changes. If the Submit Changes button is not selected, the new configuration

will not be updated and saved.

Several fields on this screen are read-only - you can view the data but not edit it. These fields

include:

Low Temperature

Warning Threshold

Enter a low temperature warning threshold - if the temperature

drops below this value, a low temperature warning is generated.

High Humidity

Warning Threshold

Enter a high humidity warning threshold - if the humidity rises above

this value, a high humidity warning is generated.

Low Humidity

Warning Threshold

Enter a low humidity warning threshold - if the humidity drops below

this value, a low humidity warning is generated.

Warning Delay

The number of seconds that pass between the time the system

goes into a warning state and the time that warning is annunciated.

Gain (Wi-ASx/Wi-

MS)

and

Offset (Wi-ASx/Wi-

MS)

Gain and offset values should be entered for Bapi sensors and

other analog sensors. Gain and offset values for sensors are as

follows:

0-5V Sensor (Bapi)

Gain: 0.012200

Offset: 0

0-10V Sensor (Bapi)

Gain: 0.024400

Offset: 0

4-20mA Sensor (Bapi)

Gain: 0.003906

Offset: 4

Move senor position

to

Reorder the sensors by typing the appropriate number in this box.

Option

Description

Table 3.15 Sensors Tab Configuration Options (continued)

Option

Description

Type (Model)

This label is derived from the value entered into the Sensor Type ID

field.

Out Of Service

A binary number used to determine if the senor is online or offline.

Raw Data #1-3

This is the uncalculated data received from the wireless sensor.

This data is then processed by the Wireless Gateway to a

calculated value.