Table 3.16, Sensors tab read-only data – RLE FDS-Wi V.2.5 User Manual
Page 39

www.rletech.com
39
970.484.6510
3
Web Interface – Standard Version
NOTE When the desired edits have been made, click the Submit Changes button to save
the changes. If the Submit Changes button is not selected, the new configuration
will not be updated and saved.
Several fields on this screen are read-only - you can view the data but not edit it. These fields
include:
Low Temperature
Warning Threshold
Enter a low temperature warning threshold - if the temperature
drops below this value, a low temperature warning is generated.
High Humidity
Warning Threshold
Enter a high humidity warning threshold - if the humidity rises above
this value, a high humidity warning is generated.
Low Humidity
Warning Threshold
Enter a low humidity warning threshold - if the humidity drops below
this value, a low humidity warning is generated.
Warning Delay
The number of seconds that pass between the time the system
goes into a warning state and the time that warning is annunciated.
Gain (Wi-ASx/Wi-
MS)
and
Offset (Wi-ASx/Wi-
MS)
Gain and offset values should be entered for Bapi sensors and
other analog sensors. Gain and offset values for sensors are as
follows:
0-5V Sensor (Bapi)
–
Gain: 0.012200
–
Offset: 0
0-10V Sensor (Bapi)
–
Gain: 0.024400
–
Offset: 0
4-20mA Sensor (Bapi)
–
Gain: 0.003906
–
Offset: 4
Move senor position
to
Reorder the sensors by typing the appropriate number in this box.
Option
Description
Table 3.15 Sensors Tab Configuration Options (continued)
Option
Description
Type (Model)
This label is derived from the value entered into the Sensor Type ID
field.
Out Of Service
A binary number used to determine if the senor is online or offline.
Raw Data #1-3
This is the uncalculated data received from the wireless sensor.
This data is then processed by the Wireless Gateway to a
calculated value.
Table 3.16 Sensors Tab Read-only Data