Web Interface – Integration Version

NOTE When the desired edits have been made, click the Submit Changes button to save

the changes. If the Submit Changes button is not selected, the new configuration

will not be updated and saved.

High Temperature

Warning Threshold

Enter a high temperature warning threshold - if the temperature

rises above this value, a high temperature warning is generated.

Low Temperature

Warning Threshold

Enter a low temperature warning threshold - if the temperature

drops below this value, a low temperature warning is generated.

High Humidity

Warning Threshold

Enter a high humidity warning threshold - if the humidity rises above

this value, a high humidity warning is generated.

Low Humidity

Warning Threshold

Enter a low humidity warning threshold - if the humidity drops below

this value, a low humidity warning is generated.

Warning Delay

The number of seconds that pass between the time the system

goes into a warning state and the time that warning is annunciated.

Gain (Wi-ASx/Wi-

MS)

and

Offset (Wi-ASx/Wi-

MS)

Gain and offset values should be entered for Bapi sensors and

other analog sensors. Gain and offset values for sensors are as

follows:

0-5V Sensor (Bapi)

Gain: 0.012200

Offset: 0

0-10V Sensor (Bapi)

Gain: 0.024400

Offset: 0

4-20mA Sensor (Bapi)

Gain: 0.003906

Offset: 4

Contact Alarm (Wi-

DIT/Wi-TC9/Bapi-

WDI)

Select One: Normally Open / Normally Closed
Select One: Alarm / Status

Move senor position

to

Reorder the sensors by typing the appropriate number in this box.

Option

Description