beautypg.com

Table 4.2, Wireless sensor configuration options – RLE FDS-Wi V.2.5 User Manual

Page 49

background image

www.rletech.com

49

970.484.6510

4

Web Interface – Integration Version

All fields in the following table will not be available for each sensor. Only the configurable

options that apply to each sensor are displayed in that sensor’s configuration menu. Editable

options are as follows:

Option

Description

Model

To edit the sensor model, select the type of model from the drop-

down list by clicking on the down arrow to the direct right of the

sensor model field.

This number is used by the Wireless Gateway to identify what kind

of sensor is being read in to the system. The possible values are:
BAPI

76

Counter

11

SetPointOverride

5B

Thermistor

57

Wi-ASx/Wi-MS

41

Wi-DIT

61

Wi-LD

76

Wi-TC9

74

Wi-TH2

52

Wi_THS

48

Wi-TS

54

Serial Number

This is the unique number broadcasted from the sensor to the

Wireless Gateway for identification. Each sensor has a unique

serial number. Enter the appropriate serial number, listed on the

bottom of the sensor, in the provided text field.

Offline Delay

Users can designate how many minutes must pass before the

Wireless Gateway considers the sensor offline. Typical

transmission time is 10-20 seconds for 418MHz sensors and 3-5

minutes for 900MHz sensors.

Location/

Description

Enter a label up to 30 characters to describe the sensor and its

location.

High Temperature/

Analog Alarm

Threshold

Enter a high alarm threshold - if the value rises above this number,

an alarm is generated for this sensor.

Low Temperature/

Analog Alarm

Threshold

Enter a low alarm threshold - if the value drops below this number,

an alarm is generated for this sensor.

High Temperature

Alarm Threshold

Enter a high temperature alarm threshold - if the temperature rises

above this value, a high temperature alarm is generated.

Low Temperature

Alarm Threshold

Enter a low temperature alarm threshold - if the temperature drops

below this value, a low temperature alarm is generated.

High Humidity Alarm

Threshold

Enter a high humidity alarm threshold - if the humidity rises above

this value, a high humidity alarm is generated.

Low Humidity Alarm

Threshold

Enter a low humidity alarm threshold - if the humidity drops below

this value, a low humidity alarm is generated.

Alarm Delay

The number of seconds that pass between the time the system

goes into alarm and the time that alarm is annunciated.

Table 4.2 Wireless Sensor Configuration Options