Minilink pd programming, Minilink pd confi guration screens, Vcm-x / rne operator interfaces technical guide 66 – Orion System VCM-X/RNE Operator Interfaces User Manual
Page 66: Minilink pd confi guration
MINILINK PD PROGRAMMING
VCM-X / RNE Operator Interfaces Technical Guide
66
MiniLink PD Confi guration Screens
MiniLink PD Confi guration
In order to correctly setup the MiniLink PD, you must fi rst confi gure
several parameters in regard to the type of system and operating param-
eters for the system it is installed on. Most of these values and operating
parameters are only set once at the initial system setup and are never
changed.
System Manager Instructions
From any Menu Screen, press the
button. The Unit
Selection Screen will appear requesting that you enter the unit ID num-
ber. All MiniLink PDs are set at address 60. Enter the correct unit loop
number for the loop the MiniLink Polling Device is connected to (Loop
1 you would enter 1) and then enter
<60>
. Press
. You will
see the screen shown below.
1) Change Setpoint
2) Configure Unit
3) Damper Force
ESC) Exit Menu
Press
<2>
on the keypad to enter the fi rst Unit Confi guration Screen.
Modular Service Tool Instructions
From any Menu Screen, press the
button. The
Unit Selection Screen will appear requesting that you enter the unit ID
number. Enter the correct unit ID number of the controller you want to
confi gure and press
. You will then see Unit Confi guration
Screen #1.
Confi guration Screen #1 - System Type
Polling Unit Config
System Type
Selection: X
[0=Zoning 1=VAV]
This screen allows you to select whether you want the system to behave
as a VAV system or a Zoning System. If you select VAV, this will allow
tenant logging for your VAV system.
Confi guration Screen #2 - Last Polled Zone
Polling Unit Config
Last Polled Zone
Address: XX
[Enter Last Zone]
This zone is the last zone on the local loop of your zoning system that
is to be included in zone voting.
Confi guration Screen #3 - Mode Changeover
Time
Polling Unit Config
Mode Changeover Time
Minutes: XX
[Enter Period Time]
This is the amount of time that you want to allow between changeover
from heating to cooling modes.
Confi guration Screen #4 - Optimal Start
Target Zone
Polling Unit Config
Optimal Start
Target Zone..: XXX
[Enter Target Zone]
This is the unit ID of the Zone that you want to be satisfi ed by the normally
scheduled start time. If you enter “-1” into this box, it will average all
zones instead of picking a specifi c zone. If you do not require Optimal
Start, enter “0”.
Confi guration Screen #5 - Maverick Testing
Polling Unit Config
Maverick Testing
Disabled: YES
[0=NO 1=YES]
Disabling the Maverick Testing allows known troubled zone(s) to con-
tinue voting without causing a Maverick alarm. In other words, all zones
are included in the voting regardless of whether they are more than four
degrees from setpoint.
Confi guration Screens #6-65 - Alarm Polling
Polling Unit Config
Enable Alarm Polling
Unit XX : YES
[0=NO 1=YES]
Enabling Alarm Polling allows any alarm from the loop to be polled.
You must set this for each controller on the loop.