Vcm-x / rne status, Vcm-x / rne status screens, Vcm-x / rne operator interfaces technical guide 56 – Orion System VCM-X/RNE Operator Interfaces User Manual
Page 56

VCM-X / RNE STATUS
VCM-X / RNE Operator Interfaces Technical Guide
56
VCM-X / RNE Status Screens
Line 2-3 Current Head Pressure Cooling or Reheat Setpoint
If you are using the VCM-X Modular, VCM-X WSHP,
or RNE Controller and have a One Condenser or Two
Condenser Head Pressure Module attached to the unit,
the Head Pressure Cooling or Reheat Setpoint will display,
depending on what mode the Module is in. This status
value will show 0 if not in the Cooling or Dehumidifi cation
Mode.
Status Screen 23 - Head Pressure Condenser
Fan #1
VCMX-M/HP Cnfg ID 102
Cond. Fan Sect. #1
Head Pr.....: 0PSI
Cond Fan Spd: 0%
Line 2 Condenser Fan #1
If you are using the VCM-X Modular, VCM-X WSHP, or
RNE Controller and have a One Condenser or Two
Condenser Head Pressure Module attached to the unit, this
line displays Condenser Fan #1.
Line 3 Head Pressure
This line indicates the highest of up to 4 current Head
Pressure readings on a One Condenser Head Pressure
Module. If using a Two Condenser Head Pressure Module,
this line indicates the highest of the fi rst 2 current Head
Pressure readings on that module.
Line 4 Condenser Fan Speed
This line displays the speed of the associated Condenser
Fan (0-100%) that is currently necessary to maintain the
Head
Pressure
Setpoint.
Status Screen 24 - Head Pressure Condenser
Fan #2
VCMX-M/HP Cnfg ID 102
Cond. Fan Sect. #2
Head Pr.....: 0PSI
Cond Fan Spd: 0%
Line 2 Condenser Fan #2
If you are using the VCM-X Modular, VCM-X WSHP,
or RNE Controller and have a Two Condenser Head
Pressure Module attached to the unit, this line displays
Condenser
Fan
#2.
Line 3 Head Pressure
This line indicates the highest of the second two Head
Pressure readings of the Two Condenser Head Pressure
Module.
Line 4 Condenser Fan Speed
This line displays the speed of the associated Condenser
Fan (0-100%) that is currently necessary to maintain the
Head
Pressure
Setpoint.
Status Screen 25 - Return Air Damper Signal
& Bypass Damper Signal
VCM-X / RNE v1.00
Return Dmp..: XXX%
Bypass Dmp..: XXX%
[Optional Outputs]
Line 2 Current Return Air Damper Signal
Indicates the current Output Signal percentage being sent to
the Return Air Damper Actuator. If you haven’t confi gured
a Return Air Bypass Damper, [No Return Dmp Confg] will
be displayed instead.
Line 3 Current Return Air Bypass Damper Signal
Indicates the current Output Signal percentage being sent to
the Return Air Bypass Damper Actuator. If you haven’t
confi gured a Return Air Bypass Damper, [No Bypass Dmp
Confg] will be displayed instead.
Line 4 Indicates That These Are Optional Outputs
This output may or may not have live data to display.
Status Screen 22 - Head Pressure Setpoint
VCMX-M/HP Cnfg ID 102
Current
Head Pr Spt: 0 PSI