Vcm-x configuration, Vcm-x confi guration screens, Vcm-x / rne operator interfaces technical guide 22 – Orion System VCM-X/RNE Operator Interfaces User Manual
Page 22

Zone
Zone
VCM-X CONFIGURATION
VCM-X / RNE Operator Interfaces Technical Guide
22
VCM-X Confi guration Screens
Confi guration Screen #20 - Modulating Cooling
Reverse Acting
VCM-X Cnfg ID 59
Mod Cooling
Rev Acting: NO
[0=NO 1=YES]
Enter
<1>
for YES if the Modulating Cooling Source requires 0 VDC
to open and 10 VDC to close. You cannot use a Reverse Acting Signal if
a Digital Compressor is being used. Enter
<0>
for NO. Default is NO.
Confi guration Screen #21 - Modulating Cooling
Proportional Window
VCM-X Cnfg ID 59
Mod Cooling
Prop. Window.: 10ºF
Time Period..: 30 s
The Modulating Cooling Proportional Window is the control range of
the Modulating Signal above and below the Active Supply Air Setpoint.
The larger the Modulating Cooling Proportional Window, the smaller
the signal adjustment per Time Period will be for each ºF the supply air
is from the Active Supply Air Temperature Setpoint. The Time Period is
the delay before another signal increase or decrease can be made and is
user-adjustable. Short Time Periods may cause hunting of the Modulat-
ing Signal. Defaults are 10ºF and 30 seconds.
Confi guration Screen #22 - Head Pressure
Module Installed
VCMX-M/HP Cnfg ID 102
Head Pressure
Module Installed: NO
[0=NO 1=YES]
Enter
<1>
for YES if you have a Head Pressure Module installed. Enter
<0>
for NO. This screen only applies if using the VCM-X Modular or
WSHP Controller. Default is NO.
Confi guration Screen #23 - Full Digital Module/
WSHP w/Multiple Digital Scroll
Compressors OR Dual Digital Module/WSHP
w/2 Digital Scroll Compressors Installed
VCMX-M/HP Cnfg ID 102
Full Digital Module
Installed: NO
[0=NO 1=YES]
If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-A) or
VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-A) is being
used, this screen will appear. Enter
<1>
for YES if you have either a
Full Digital Module installed or if you have a Water Source Heat Pump
Module installed and in both cases all the compressors in the unit are
Digital Scroll Compressors (2 Digital Compressors only or all 4 Digital
Compressors). If you have a combination of Digital Compressors and
Fixed Compressors, enter
<0>
for NO.
VCMX-M/HP Cnfg ID 102
Dual Digital Module
Installed: NO
[0=NO 1=YES]
If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-C) or
VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-C) is being used,
this screen will appear. Enter
<1>
for YES if you have a Dual Digital
Module installed or if the VCM-X WSHP Controller has two Digital
Scroll Compressors. Enter
<0>
for NO.
Confi guration Screen #24 - Split Condenser
VCMX-M/HP Cnfg ID 102
Is this a
Split Condenser: NO
[0=NO 1=YES]
Enter
<1>
for YES if you have a Split Condenser with two physically
separate condenser sections. This requires a Two Condenser Head Pres-
sure Module. Enter
<0>
for NO. This screen only applies if using the
VCM-X or WSHP Modular Controller. Default is NO.