VCM-X / RNE STATUS
VCM-X / RNE Operator Interfaces Technical Guide
51
VCM-X / RNE Status Screens
Status Screen 8 - Coil Temp & Setpoint
VCM-X / RNE v1.00
Coil Tmp...: XX.XºF
Coil Tmp Spt: XX.XºF
Line 2 Coil Temperature or Lowest Coil
If a Suction Pressure Transducer has been installed and
confi gured on the unit, the calculated Evaporator Coil
Temperature will appear on this line. If not, this line will
display
0°F.
If this unit has multiple digital scroll compressors and has a
Full Digital Module or Dual Digital Module installed, this
line will display Lowest Coil and will display the lowest of
the multiple suction temperatures. The coil temperatures of
all the coils will be displayed on Status Screens 19 & 20.
Line 3 Coil Temperature Setpoint
During
dehumidifi cation, the Coil Suction Temperature
Setpoint is automatically reset based on the current space
humidity conditions. This is the current calculated Coil
Temperature Setpoint based on that reset.
Status Screen 9 - Outdoor Air Temperature &
Outdoor Air Relative Humidity
VCM-X / RNE v1.00
Outdoor Tmp: XX.XºF
Outdoor RH.: XX.X%
Line 2 Current Outdoor Air Temperature
If an Outdoor Air Temperature Sensor has been installed
and
confi gured on the unit or if an Outdoor Air Broadcast
has
been
confi gured on another VCM-X or RNE Controller
on the system, the Outdoor Air Temperature will appear on
this line. If not, this line will display a temperature that is
half way between the Cooling and Heating Lockout
Setpoints.
Line 3 Current Outdoor Air Relative Humidity
If an Outdoor Humidity Sensor has been installed and
confi gured on the VCM-X or RNE, the Outdoor Air
Relative Humidity Percentage will appear on this line. If
not, this line will display 0%.
Status Screen 10 - OA Dewpoint & Dewpoint
Temp
VCM-X / RNE v1.00
OA Dewpoint.: XX.XºF
Dewpoint Spt: XX.XºF
Line 2 Current Calculated Outdoor Air Dewpoint
Temperature
If both an Outdoor Humidity Sensor and an Outdoor Air
Temperature Sensor have been installed and confi gured on
the unit, the calculated Outdoor Air Dewpoint Temperature
will appear on this line. If not, this screen displays 0°F.
Line 3 Current Outdoor Air Dewpoint Setpoint
The user adjustable Outdoor Air Dewpoint Temperature
Setpoint will appear on this line.
Status Screen 11 - Indoor RH & Indoor RH
Setpoint
VCM-X / RNE v1.00
Indoor RH....: XXX%
Indoor RH Spt: XXX%
Line 2 Current Indoor Relative Humidity Percentage
If an Indoor Humidity Sensor has been installed and
confi gured on the unit, the current Indoor Air Relative
Humidity Percentage will appear on this line. The installed
Indoor Humidity Sensor can be either a Wall Mounted type
or a Return Air Mounted type. If an Indoor Humidity
Sensor is not installed, this line will display 0%.
Line 3 Current Indoor Relative Humidity Setpoint Percentage
This is the adjustable Indoor Air Relative Humidity
Setpoint Percentage that has been set by the user.